EA-340AG4-C01 C
19.27 kW
Defrost: None
Product code: EA-250AE10-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,381 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 47.5 m² |
| Inner volume | 22.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 112 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,420 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-250AE10-C09 C | None |
|---|---|
| EA-250AE10-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.98 | 6.85 | 6.77 | 6.71 | 6.63 | 6.53 | 6.42 | 6.48 | 6.84 | 7.36 | 7.14 | 7.06 | 6.95 | 6.79 |
| 5 | 9.42 | 9.39 | 9.38 | 9.39 | 9.32 | 9.22 | 9.07 | 9.13 | 9.67 | 10.42 | 10.10 | 9.99 | 9.84 | 9.60 |
| 6 | 11.83 | 11.95 | 12.08 | 12.20 | 12.21 | 12.13 | 11.99 | 12.06 | 12.76 | 13.75 | 13.30 | 13.14 | 12.92 | 12.57 |
| 7 | 14.20 | 14.51 | 14.81 | 15.08 | 15.18 | 15.18 | 15.07 | 15.14 | 16.03 | 17.30 | 16.73 | 16.51 | 16.19 | 15.68 |
| 8 | 16.36 | 16.89 | 17.41 | 17.89 | 18.18 | 18.28 | 18.22 | 18.33 | 19.41 | 21.00 | 20.34 | 20.08 | 19.69 | 19.05 |
| 9 | 18.24 | 18.99 | 19.70 | 20.35 | 20.73 | 21.01 | 21.13 | 21.37 | 22.69 | 24.63 | 24.02 | 23.72 | 23.28 | 22.54 |
| 10 | 19.99 | 21.00 | 21.84 | 22.69 | 23.26 | 23.64 | 23.84 | 24.13 | 25.63 | 27.83 | 27.21 | 26.94 | 26.52 | 25.81 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 27.213 |
| SC2 | 0 | 8 | 18.329 |
| SC3 | -18 | 7 | 15.118 |
| SC4 | -25 | 6 | 12.079 |
| SC5 | -34 | 6 | 11.868 |
| A | 2087 mm |
|---|---|
| B | 640 mm |
| C | 685 mm |
| F | 445 mm |
| E1 | 868 mm |
| E | 1735 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2087 mm |
|---|---|
| Width | 640 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.