EA-263ED10-C01 C
19.87 kW
Defrost: None
Product code: EA-263EC7-C06 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 18,012 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 90.1 m² |
| Inner volume | 27.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 168 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 1,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.5 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-263EC7-C06 C | None |
|---|---|
| EA-263EC7-C06 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.64 | 7.51 | 7.45 | 7.44 | 7.40 | 7.36 | 7.32 | 7.40 | 7.84 | 8.48 | 8.31 | 8.24 | 8.15 | 8.01 |
| 5 | 10.14 | 10.07 | 10.05 | 10.06 | 10.02 | 9.96 | 9.87 | 9.96 | 10.57 | 11.43 | 11.16 | 11.07 | 10.92 | 10.70 |
| 6 | 12.71 | 12.75 | 12.81 | 12.89 | 12.87 | 12.80 | 12.70 | 12.76 | 13.52 | 14.61 | 14.22 | 14.08 | 13.88 | 13.58 |
| 7 | 15.17 | 15.40 | 15.61 | 15.81 | 15.87 | 15.84 | 15.73 | 15.78 | 16.69 | 18.02 | 17.51 | 17.32 | 17.04 | 16.62 |
| 8 | 17.51 | 17.90 | 18.32 | 18.69 | 18.88 | 18.92 | 18.85 | 18.91 | 20.03 | 21.64 | 21.01 | 20.76 | 20.41 | 19.85 |
| 9 | 19.53 | 20.21 | 20.85 | 21.44 | 21.82 | 22.04 | 22.06 | 22.16 | 23.47 | 25.39 | 24.67 | 24.39 | 23.97 | 23.29 |
| 10 | 21.40 | 22.33 | 23.19 | 23.96 | 24.47 | 24.79 | 24.95 | 25.17 | 26.72 | 29.00 | 28.35 | 28.09 | 27.63 | 26.84 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.77 | 6.65 | 6.60 | 6.59 | 6.57 | 6.55 | 6.52 | 6.62 | 7.02 | 7.61 | 7.47 | 7.42 | 7.34 | 7.24 |
| 5 | 8.94 | 8.84 | 8.81 | 8.82 | 8.79 | 8.74 | 8.69 | 8.77 | 9.31 | 10.08 | 9.86 | 9.78 | 9.68 | 9.54 |
| 6 | 11.19 | 11.15 | 11.14 | 11.20 | 11.19 | 11.13 | 11.05 | 11.12 | 11.79 | 12.74 | 12.42 | 12.30 | 12.14 | 11.89 |
| 7 | 13.38 | 13.46 | 13.57 | 13.69 | 13.72 | 13.67 | 13.57 | 13.62 | 14.43 | 15.59 | 15.16 | 15.00 | 14.77 | 14.41 |
| 8 | 15.49 | 15.74 | 15.98 | 16.21 | 16.31 | 16.31 | 16.22 | 16.25 | 17.20 | 18.59 | 18.05 | 17.84 | 17.54 | 17.08 |
| 9 | 17.50 | 17.95 | 18.31 | 18.68 | 18.89 | 18.95 | 18.91 | 18.96 | 20.08 | 21.71 | 21.08 | 20.84 | 20.47 | 19.90 |
| 10 | 19.28 | 19.91 | 20.52 | 21.09 | 21.46 | 21.64 | 21.65 | 21.73 | 23.02 | 24.90 | 24.21 | 23.93 | 23.51 | 22.84 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 28.352 | 24.209 |
| SC2 | 0 | 8 | 18.914 | 16.246 |
| SC3 | -18 | 7 | 15.849 | 13.709 |
| SC4 | -25 | 6 | 12.813 | 11.144 |
| SC5 | -34 | 6 | 12.736 | 11.195 |
| A | 2015 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2015 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.