EA-350AC10-C10 C
21.59 kW
Defrost: None
Product code: EA-263ED7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,695 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 112.3 m² |
| Inner volume | 32.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 190 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 77.1 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| EA-263ED7-C01 C | None |
|---|---|
| EA-263ED7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.26 | 8.19 | 8.17 | 8.18 | 8.16 | 8.12 | 8.07 | 8.19 | 8.68 | 9.39 | 9.19 | 9.11 | 9.01 | 8.85 |
| 5 | 10.90 | 10.93 | 10.96 | 11.03 | 11.03 | 10.97 | 10.89 | 11.00 | 11.68 | 12.64 | 12.33 | 12.23 | 12.08 | 11.86 |
| 6 | 13.45 | 13.67 | 13.87 | 14.06 | 14.11 | 14.07 | 13.97 | 14.07 | 14.92 | 16.12 | 15.68 | 15.53 | 15.30 | 14.96 |
| 7 | 15.89 | 16.36 | 16.77 | 17.06 | 17.24 | 17.28 | 17.21 | 17.31 | 18.34 | 19.82 | 19.25 | 19.04 | 18.73 | 18.24 |
| 8 | 18.16 | 18.83 | 19.50 | 20.08 | 20.41 | 20.56 | 20.55 | 20.68 | 21.91 | 23.71 | 23.03 | 22.77 | 22.37 | 21.73 |
| 9 | 20.03 | 21.02 | 21.93 | 22.74 | 23.28 | 23.61 | 23.77 | 24.02 | 25.51 | 27.70 | 26.94 | 26.63 | 26.15 | 25.38 |
| 10 | 21.81 | 23.11 | 24.29 | 25.32 | 26.04 | 26.48 | 26.72 | 27.02 | 28.70 | 31.16 | 30.47 | 30.17 | 29.71 | 28.95 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 30.469 |
| SC2 | 0 | 8 | 20.678 |
| SC3 | -18 | 7 | 17.150 |
| SC4 | -25 | 6 | 13.874 |
| SC5 | -34 | 6 | 13.519 |
| A | 2015 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 2015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.