EA-250AE6-C10 C
23.63 kW
Defrost: None
Product code: EA-263EE10-C06 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 17,145 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 97.7 m² |
| Inner volume | 41.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 201 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 1,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.1 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-263EE10-C06 C | None |
|---|---|
| EA-263EE10-C06 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.24 | 9.11 | 9.05 | 9.03 | 8.97 | 8.90 | 8.81 | 8.92 | 9.45 | 10.21 | 9.97 | 9.87 | 9.75 | 9.55 |
| 5 | 12.18 | 12.15 | 12.16 | 12.19 | 12.15 | 12.06 | 11.94 | 12.03 | 12.75 | 13.78 | 13.41 | 13.28 | 13.10 | 12.84 |
| 6 | 15.15 | 15.27 | 15.40 | 15.54 | 15.53 | 15.46 | 15.32 | 15.39 | 16.30 | 17.60 | 17.08 | 16.89 | 16.62 | 16.21 |
| 7 | 17.94 | 18.29 | 18.62 | 18.92 | 19.04 | 19.02 | 18.88 | 18.94 | 20.05 | 21.65 | 20.99 | 20.74 | 20.35 | 19.77 |
| 8 | 20.58 | 21.22 | 21.80 | 22.21 | 22.49 | 22.57 | 22.51 | 22.59 | 23.91 | 25.85 | 25.05 | 24.74 | 24.28 | 23.53 |
| 9 | 23.04 | 23.87 | 24.72 | 25.49 | 25.95 | 26.17 | 26.19 | 26.31 | 27.87 | 30.14 | 29.27 | 28.90 | 28.36 | 27.45 |
| 10 | 25.08 | 26.30 | 27.42 | 28.42 | 29.08 | 29.49 | 29.70 | 29.98 | 31.82 | 34.48 | 33.54 | 33.13 | 32.52 | 31.48 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.06 | 7.92 | 7.86 | 7.85 | 7.81 | 7.76 | 7.70 | 7.80 | 8.30 | 8.98 | 8.78 | 8.71 | 8.61 | 8.45 |
| 5 | 10.59 | 10.50 | 10.48 | 10.49 | 10.46 | 10.40 | 10.31 | 10.38 | 11.00 | 11.90 | 11.60 | 11.50 | 11.35 | 11.13 |
| 6 | 13.17 | 13.13 | 13.19 | 13.27 | 13.27 | 13.21 | 13.11 | 13.16 | 13.93 | 15.06 | 14.63 | 14.47 | 14.25 | 13.91 |
| 7 | 15.65 | 15.79 | 15.96 | 16.14 | 16.18 | 16.15 | 16.05 | 16.08 | 17.03 | 18.39 | 17.85 | 17.64 | 17.32 | 16.80 |
| 8 | 18.02 | 18.36 | 18.69 | 19.01 | 19.15 | 19.17 | 19.09 | 19.12 | 20.23 | 21.87 | 21.19 | 20.90 | 20.47 | 19.75 |
| 9 | 20.27 | 20.84 | 21.38 | 21.79 | 22.07 | 22.17 | 22.14 | 22.20 | 23.50 | 25.40 | 24.59 | 24.25 | 23.73 | 22.82 |
| 10 | 22.38 | 23.14 | 23.90 | 24.58 | 24.98 | 25.19 | 25.22 | 25.33 | 26.83 | 29.00 | 28.10 | 27.70 | 27.09 | 25.95 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 33.543 | 28.104 |
| SC2 | 0 | 8 | 22.586 | 19.116 |
| SC3 | -18 | 7 | 18.985 | 16.174 |
| SC4 | -25 | 6 | 15.401 | 13.188 |
| SC5 | -34 | 6 | 15.192 | 13.186 |
| A | 2015 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.