EA-563FC10-C19 C
53.59 kW
Defrost: None
Product code: EA-263FG4-C08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 25,777 m³/h |
|---|---|
| Air throw | 35 m |
| External surface | 334.1 m² |
| Inner volume | 68.6 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 330 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-263FG4-C08 C | None |
|---|---|
| EA-263FG4-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 21.43 | 21.26 | 21.24 | 21.33 | 21.32 | 21.26 | 21.14 | 21.68 | 23.12 | 25.13 | 24.69 | 24.52 | 24.29 | 23.95 |
| 5 | 28.03 | 28.03 | 28.09 | 28.28 | 28.29 | 28.16 | 27.91 | 28.41 | 30.20 | 32.75 | 32.02 | 31.78 | 31.45 | 30.97 |
| 6 | 34.50 | 34.90 | 35.30 | 35.69 | 35.78 | 35.61 | 35.27 | 35.69 | 37.86 | 40.98 | 39.86 | 39.46 | 38.89 | 38.04 |
| 7 | 40.73 | 41.68 | 42.54 | 43.13 | 43.44 | 43.39 | 43.02 | 43.36 | 45.94 | 49.66 | 48.11 | 47.53 | 46.67 | 45.33 |
| 8 | 46.56 | 47.92 | 49.36 | 50.65 | 51.28 | 51.41 | 51.08 | 51.38 | 54.39 | 58.81 | 56.88 | 56.12 | 54.99 | 53.17 |
| 9 | 51.40 | 53.56 | 55.54 | 57.29 | 58.38 | 58.89 | 58.93 | 59.49 | 63.08 | 68.20 | 65.99 | 65.06 | 63.68 | 61.40 |
| 10 | 56.07 | 58.94 | 61.55 | 63.82 | 65.28 | 66.00 | 66.16 | 66.77 | 70.79 | 76.64 | 74.56 | 73.63 | 72.24 | 69.85 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 18.67 | 19.92 | 21.67 | 21.35 | 21.25 | 21.12 | 20.89 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 24.11 | 25.64 | 27.84 | 27.23 | 27.02 | 26.74 | 26.35 |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | 35.62 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | 41.58 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | 47.27 | 48.35 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | 52.61 | 54.14 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 74.556 | — |
| SC2 | 0 | 8 | 51.377 | — |
| SC3 | -18 | 7 | 43.303 | — |
| SC4 | -25 | 6 | 35.304 | — |
| SC5 | -34 | 6 | 34.632 | — |
| A | 2415 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| G | 1135 mm |
| E1 | 1018 mm |
| E | 2035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 2415 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.