EA-445AG6-C01 C
40.15 kW
Defrost: None
Product code: EA-263FG7-C19 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 21,932 m³/h |
|---|---|
| Air throw | 28 m |
| External surface | 225.3 m² |
| Inner volume | 66.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 271 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-263FG7-C19 C | None |
|---|---|
| EA-263FG7-C19 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.83 | 15.71 | 15.69 | 15.73 | 15.72 | 15.67 | 15.58 | 15.79 | 16.79 | 18.18 | 17.81 | 17.66 | 17.47 | 17.17 |
| 5 | 20.61 | 20.67 | 20.80 | 20.95 | 20.98 | 20.92 | 20.78 | 20.96 | 22.24 | 24.07 | 23.49 | 23.29 | 23.01 | 22.58 |
| 6 | 25.41 | 25.76 | 26.11 | 26.45 | 26.54 | 26.52 | 26.38 | 26.53 | 28.11 | 30.40 | 29.59 | 29.29 | 28.86 | 28.20 |
| 7 | 29.92 | 30.68 | 31.38 | 32.00 | 32.31 | 32.38 | 32.22 | 32.34 | 34.27 | 37.06 | 36.02 | 35.62 | 35.03 | 34.10 |
| 8 | 34.15 | 35.42 | 36.38 | 37.37 | 37.95 | 38.22 | 38.20 | 38.39 | 40.67 | 44.01 | 42.76 | 42.27 | 41.52 | 40.35 |
| 9 | 37.77 | 39.55 | 41.13 | 42.55 | 43.51 | 44.08 | 44.25 | 44.53 | 47.20 | 51.09 | 49.70 | 49.12 | 48.27 | 46.86 |
| 10 | 41.23 | 43.47 | 45.52 | 47.34 | 48.57 | 49.37 | 49.78 | 50.30 | 53.40 | 57.93 | 56.64 | 56.08 | 55.13 | 53.50 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.86 | 13.71 | 13.68 | 13.72 | 13.72 | 13.69 | 13.63 | 13.86 | 14.75 | 16.01 | 15.72 | 15.63 | 15.47 | 15.23 |
| 5 | 17.99 | 17.94 | 17.99 | 18.10 | 18.11 | 18.06 | 17.95 | 18.15 | 19.27 | 20.89 | 20.41 | 20.24 | 20.00 | 19.66 |
| 6 | 22.19 | 22.30 | 22.44 | 22.67 | 22.75 | 22.70 | 22.56 | 22.73 | 24.10 | 26.08 | 25.40 | 25.14 | 24.78 | 24.21 |
| 7 | 26.19 | 26.59 | 26.99 | 27.39 | 27.56 | 27.54 | 27.40 | 27.54 | 29.17 | 31.56 | 30.65 | 30.29 | 29.75 | 28.88 |
| 8 | 30.02 | 30.76 | 31.46 | 32.10 | 32.43 | 32.51 | 32.40 | 32.49 | 34.40 | 37.20 | 36.06 | 35.58 | 34.88 | 33.69 |
| 9 | 33.62 | 34.78 | 35.71 | 36.64 | 37.19 | 37.41 | 37.38 | 37.57 | 39.78 | 42.99 | 41.67 | 41.08 | 40.22 | 38.72 |
| 10 | 36.98 | 38.41 | 39.85 | 41.16 | 41.97 | 42.38 | 42.46 | 42.71 | 45.23 | 48.87 | 47.40 | 46.73 | 45.71 | 43.90 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 56.642 | 47.395 |
| SC2 | 0 | 8 | 38.387 | 32.490 |
| SC3 | -18 | 7 | 32.157 | 27.479 |
| SC4 | -25 | 6 | 26.110 | 22.442 |
| SC5 | -34 | 6 | 25.522 | 22.242 |
| A | 2415 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E1 | 1018 mm |
| E | 2035 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2415 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.