EA-180GD10-C01 C
21.95 kW
Defrost: None
Product code: EA-345AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,099 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 54.8 m² |
| Inner volume | 25.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 127 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-345AE10-C01 C | None |
|---|---|
| EA-345AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.97 | 7.99 | 8.02 | 8.05 | 8.01 | 7.93 | 7.81 | 7.95 | 8.40 | 9.05 | 8.78 | 8.68 | 8.54 | 8.33 |
| 5 | 10.50 | 10.72 | 10.92 | 11.09 | 11.14 | 11.10 | 10.99 | 11.13 | 11.81 | 12.76 | 12.39 | 12.27 | 12.09 | 11.83 |
| 6 | 12.97 | 13.43 | 13.85 | 14.21 | 14.37 | 14.44 | 14.38 | 14.54 | 15.42 | 16.68 | 16.18 | 15.99 | 15.72 | 15.29 |
| 7 | 15.16 | 15.86 | 16.52 | 17.12 | 17.53 | 17.77 | 17.82 | 18.03 | 19.12 | 20.73 | 20.16 | 19.93 | 19.59 | 19.01 |
| 8 | 17.04 | 18.02 | 18.93 | 19.65 | 20.22 | 20.60 | 20.80 | 21.12 | 22.46 | 24.44 | 23.90 | 23.68 | 23.32 | 22.74 |
| 9 | 18.76 | 19.90 | 21.11 | 22.17 | 22.94 | 23.46 | 23.76 | 24.15 | 25.69 | 27.94 | 27.36 | 27.10 | 26.69 | 26.00 |
| 10 | 20.34 | 21.81 | 23.29 | 24.62 | 25.58 | 26.27 | 26.69 | 27.18 | 28.92 | 31.47 | 30.85 | 30.56 | 30.10 | 29.30 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 30.853 |
| SC2 | 0 | 8 | 21.124 |
| SC3 | -18 | 7 | 17.304 |
| SC4 | -25 | 6 | 13.846 |
| SC5 | -34 | 6 | 13.084 |
| A | 2467 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2135 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2467 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.