EA-250AG6-C10 C
27.28 kW
Defrost: None
Product code: EA-345AE6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,956 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 86.3 m² |
| Inner volume | 26.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 131 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø54 |
| EA-345AE6-C01 C | None |
|---|---|
| EA-345AE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.33 | 10.24 | 10.20 | 10.19 | 10.14 | 10.04 | 9.92 | 10.18 | 10.82 | 11.70 | 11.42 | 11.32 | 11.18 | 10.97 |
| 5 | 13.69 | 13.75 | 13.84 | 13.93 | 13.90 | 13.79 | 13.61 | 13.84 | 14.70 | 15.91 | 15.48 | 15.35 | 15.16 | 14.90 |
| 6 | 17.05 | 17.34 | 17.62 | 17.83 | 17.91 | 17.84 | 17.65 | 17.84 | 18.91 | 20.43 | 19.78 | 19.55 | 19.22 | 18.73 |
| 7 | 20.17 | 20.75 | 21.32 | 21.81 | 22.04 | 22.06 | 21.88 | 22.05 | 23.36 | 25.25 | 24.42 | 24.10 | 23.62 | 22.87 |
| 8 | 22.84 | 23.72 | 24.54 | 25.27 | 25.66 | 25.90 | 25.94 | 26.23 | 27.84 | 30.21 | 29.25 | 28.85 | 28.26 | 27.29 |
| 9 | 25.35 | 26.56 | 27.55 | 28.54 | 29.19 | 29.53 | 29.64 | 29.98 | 31.81 | 34.49 | 33.60 | 33.21 | 32.62 | 31.62 |
| 10 | 27.67 | 29.12 | 30.56 | 31.83 | 32.66 | 33.16 | 33.36 | 33.77 | 35.83 | 38.84 | 37.86 | 37.41 | 36.72 | 35.55 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 37.857 |
| SC2 | 0 | 8 | 26.233 |
| SC3 | -18 | 7 | 21.929 |
| SC4 | -25 | 6 | 17.617 |
| SC5 | -34 | 6 | 17.133 |
| A | 2467 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2135 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø54 |
| Length | 2467 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.