EA-163GE7-C19 C
21.26 kW
Defrost: None
Product code: EA-350AC10-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 21,722 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 47.0 m² |
| Inner volume | 20.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 133 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 2,130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.8 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-350AC10-C09 C | None |
|---|---|
| EA-350AC10-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.50 | 7.46 | 7.44 | 7.42 | 7.34 | 7.23 | 7.11 | 7.09 | 7.47 | 8.02 | 7.75 | 7.64 | 7.50 | 7.28 |
| 5 | 10.04 | 10.21 | 10.36 | 10.48 | 10.49 | 10.43 | 10.31 | 10.33 | 10.93 | 11.77 | 11.39 | 11.25 | 11.05 | 10.72 |
| 6 | 12.53 | 12.95 | 13.32 | 13.64 | 13.81 | 13.84 | 13.79 | 13.86 | 14.68 | 15.84 | 15.35 | 15.17 | 14.91 | 14.51 |
| 7 | 14.63 | 15.28 | 15.89 | 16.44 | 16.76 | 17.01 | 17.16 | 17.38 | 18.47 | 20.07 | 19.57 | 19.37 | 19.06 | 18.56 |
| 8 | 16.49 | 17.42 | 18.17 | 18.93 | 19.48 | 19.86 | 20.10 | 20.38 | 21.68 | 23.58 | 23.13 | 22.95 | 22.68 | 22.21 |
| 9 | 18.21 | 19.31 | 20.42 | 21.43 | 22.17 | 22.70 | 23.05 | 23.41 | 24.91 | 27.12 | 26.64 | 26.44 | 26.13 | 25.61 |
| 10 | 19.67 | 21.17 | 22.58 | 23.85 | 24.81 | 25.51 | 25.99 | 26.44 | 28.16 | 30.68 | 30.19 | 29.97 | 29.63 | 29.04 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 30.189 |
| SC2 | 0 | 8 | 20.382 |
| SC3 | -18 | 7 | 16.608 |
| SC4 | -25 | 6 | 13.323 |
| SC5 | -34 | 6 | 12.635 |
| A | 2937 mm |
|---|---|
| B | 590 mm |
| C | 715 mm |
| F | 510 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 2586 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 2937 mm |
|---|---|
| Width | 590 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.