Skip to Content

Unit cooler EA-363EE7-C01 C

Unit cooler EA-363EE7-C01 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-363EE7-C01 C

Cooling capacity i
35.99 kW
Air flow
23,906 m³/h
Fin spacing
7.0 mm
Air throw
22 m
Fans
3 × ⌀630 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA — EA - general-purpose unit cooler
  • B
    Number of fans: 3 — Number of fans (one digit).
  • C
    Fan diameter: 63 — Ø630 mm
  • D
    Dimensional data - coil size letter: E — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: E — 6 tube rows
  • F
    Fin spacing: 7 — Fin spacing about 7 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 01 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole; Ø630: 230V/1Ph/50Hz, 6-pole; Ø800: 400V/3Ph/50Hz, 6-pole

Data

Evaporator
Air flow 23,906 m³/h
Air throw 22 m
External surface 202.8 m²
Inner volume 60.6 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 294 kg
Fans
Quantity 3
Diameter 630 mm
Speed 860 rpm
Power 1,800 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 79.3 dB(A)
Energy class C
Connections
Inlet Ø35
Outlet Ø54
Defrost
EA-363EE7-C01 C None
EA-363EE7-C01 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
34.435 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 14.18 14.01 13.96 13.97 13.94 13.87 13.78 14.07 14.93 16.18 15.85 15.73 15.56 15.31
5 18.60 18.57 18.61 18.69 18.67 18.57 18.42 18.68 19.84 21.48 20.99 20.82 20.58 20.24
6 23.10 23.29 23.50 23.72 23.73 23.65 23.45 23.67 25.10 27.15 26.41 26.15 25.78 25.22
7 27.38 27.91 28.41 28.85 29.03 28.99 28.79 28.96 30.69 33.17 32.17 31.80 31.27 30.44
8 31.42 32.39 33.13 33.89 34.28 34.39 34.25 34.44 36.47 39.44 38.23 37.77 37.08 35.97
9 35.18 36.42 37.69 38.85 39.59 39.88 39.84 40.07 42.45 45.92 44.56 44.00 43.17 41.81
10 38.30 40.14 41.83 43.33 44.29 44.87 45.12 45.57 48.36 52.44 51.01 50.37 49.41 47.81

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 51.008
SC2 0 8 34.435
SC3 -18 7 28.953
SC4 -25 6 23.501
SC5 -34 6 23.174

Dimensions

Dimension drawing of EA-363EE7-C01 C
Dimension drawing
Dimensions as drawn
A 2815 mm
B 1000 mm
C 1190 mm
F 960 mm
E1 818 mm
E2 800 mm
E 2435 mm
D IN 1 x Ø35
D OUT 1 x Ø54
Overall [mm]
Length 2815 mm
Width 1000 mm
Height 1190 mm

Downloads