Skip to Content

Unit cooler EA-363GC10-C08 C

Unit cooler EA-363GC10-C08 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-363GC10-C08 C

Cooling capacity i
44.37 kW
Air flow
51,545 m³/h
Fin spacing
10.0 mm
Air throw
45 m
Fans
3 × ⌀630 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA — EA - general-purpose unit cooler
  • B
    Number of fans: 3 — Number of fans (one digit).
  • C
    Fan diameter: 63 — Ø630 mm
  • D
    Dimensional data - coil size letter: G — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: C — 4 tube rows
  • F
    Fin spacing: 10 — Fin spacing about 10 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 08 — Ø630: 400V/3Ph/50Hz, 4-pole

Data

Evaporator
Air flow 51,545 m³/h
Air throw 45 m
External surface 158.7 m²
Inner volume 67.0 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 377 kg
Fans
Quantity 3
Diameter 630 mm
Speed 1,340 rpm
Power 5,700 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 74.0 dB(A)
Sound power 97.0 dB(A)
Energy class E
Connections
Inlet Ø42
Outlet Ø66,7
Defrost
EA-363GC10-C08 C None
EA-363GC10-C08 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
42.266 kW
Low speed (Y)
36.942 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 17.07 16.59 16.30 16.13 15.95 15.77 15.61 15.57 16.46 17.76 17.31 17.14 16.91 16.57
5 23.07 22.63 22.37 22.22 21.99 21.74 21.47 21.38 22.60 24.35 23.64 23.38 23.01 22.46
6 29.26 28.99 28.87 28.79 28.62 28.34 28.02 27.87 29.44 31.70 30.72 30.36 29.85 29.08
7 35.28 35.35 35.50 35.68 35.63 35.39 35.07 34.90 36.87 39.70 38.45 37.98 37.31 36.26
8 41.07 41.60 42.13 42.64 42.71 42.65 42.41 42.27 44.68 48.15 46.67 46.10 45.27 43.96
9 46.54 47.45 48.49 49.41 49.89 50.04 49.94 49.88 52.77 56.96 55.29 54.64 53.67 52.11
10 51.12 52.68 54.18 55.59 56.53 57.12 57.45 57.62 61.01 65.95 64.15 63.42 62.34 60.56

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 15.29 14.86 14.61 14.49 14.37 14.24 14.13 14.12 14.94 16.15 15.76 15.62 15.43 15.14
5 20.55 20.11 19.86 19.73 19.57 19.38 19.17 19.12 20.22 21.82 21.24 21.02 20.72 20.26
6 26.01 25.60 25.44 25.39 25.24 25.03 24.76 24.66 26.07 28.10 27.28 26.98 26.56 25.91
7 31.39 31.24 31.24 31.33 31.23 31.04 30.75 30.64 32.39 34.91 33.86 33.47 32.91 32.04
8 36.63 36.80 37.06 37.37 37.43 37.32 37.04 36.94 39.06 42.12 40.81 40.33 39.64 38.53
9 41.67 42.24 42.84 43.44 43.62 43.66 43.48 43.44 45.94 49.53 48.10 47.54 46.69 45.34
10 46.44 47.35 48.38 49.33 49.87 50.10 50.04 50.02 52.95 57.21 55.64 54.98 54.02 52.45

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 64.14555.638
SC2 0 8 42.26636.942
SC3 -18 7 35.68431.285
SC4 -25 6 28.86825.439
SC5 -34 6 29.24025.962

Dimensions

Dimension drawing of EA-363GC10-C08 C
Dimension drawing
Dimensions as drawn
A 4315 mm
B 900 mm
C 1190 mm
F 860 mm
G 935 mm
E1 1318 mm
E2 1300 mm
E 3935 mm
D IN 1 x Ø42
D OUT 1 x Ø66,7
Overall [mm]
Length 4315 mm
Width 900 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.