EA-150AC7-C09 C
8.37 kW
Defrost: None
Product code: EA-430AE10-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,428 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 30.5 m² |
| Inner volume | 13.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 59 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-430AE10-C05 C | None |
|---|---|
| EA-430AE10-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.26 | 3.24 | 3.24 | 3.25 | 3.25 | 3.23 | 3.20 | 3.27 | 3.49 | 3.78 | 3.71 | 3.68 | 3.65 | 3.58 |
| 5 | 4.26 | 4.28 | 4.32 | 4.36 | 4.38 | 4.36 | 4.32 | 4.39 | 4.66 | 5.05 | 4.92 | 4.87 | 4.81 | 4.72 |
| 6 | 5.23 | 5.32 | 5.41 | 5.50 | 5.55 | 5.55 | 5.50 | 5.57 | 5.91 | 6.40 | 6.21 | 6.13 | 6.03 | 5.86 |
| 7 | 6.20 | 6.33 | 6.50 | 6.65 | 6.73 | 6.76 | 6.73 | 6.80 | 7.20 | 7.80 | 7.56 | 7.46 | 7.31 | 7.06 |
| 8 | 7.09 | 7.34 | 7.58 | 7.80 | 7.92 | 7.98 | 7.97 | 8.05 | 8.53 | 9.23 | 8.96 | 8.84 | 8.66 | 8.35 |
| 9 | 7.92 | 8.28 | 8.61 | 8.91 | 9.11 | 9.21 | 9.22 | 9.32 | 9.88 | 10.69 | 10.39 | 10.25 | 10.03 | 9.66 |
| 10 | 8.67 | 9.12 | 9.54 | 9.92 | 10.19 | 10.32 | 10.40 | 10.55 | 11.19 | 12.14 | 11.81 | 11.66 | 11.42 | 11.00 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.814 |
| SC2 | 0 | 8 | 8.049 |
| SC3 | -18 | 7 | 6.688 |
| SC4 | -25 | 6 | 5.411 |
| SC5 | -34 | 6 | 5.258 |
| A | 2107 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 455 mm |
| E2 | 437.5 mm |
| E | 1785 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.