EA-145AG6-C01 C
9.86 kW
Defrost: None
Product code: EA-430AE6-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,039 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 47.9 m² |
| Inner volume | 13.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 60 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-430AE6-C05 C | None |
|---|---|
| EA-430AE6-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.91 | 3.93 | 3.97 | 4.01 | 4.03 | 4.02 | 3.99 | 4.11 | 4.39 | 4.78 | 4.69 | 4.66 | 4.63 | 4.59 |
| 5 | 5.00 | 5.09 | 5.19 | 5.28 | 5.32 | 5.31 | 5.27 | 5.38 | 5.72 | 6.21 | 6.05 | 5.99 | 5.91 | 5.78 |
| 6 | 6.05 | 6.23 | 6.40 | 6.56 | 6.64 | 6.66 | 6.62 | 6.71 | 7.12 | 7.72 | 7.49 | 7.40 | 7.26 | 7.03 |
| 7 | 7.09 | 7.36 | 7.62 | 7.85 | 7.97 | 8.02 | 7.99 | 8.09 | 8.57 | 9.29 | 9.00 | 8.88 | 8.69 | 8.39 |
| 8 | 8.01 | 8.40 | 8.77 | 9.09 | 9.30 | 9.40 | 9.39 | 9.49 | 10.05 | 10.88 | 10.54 | 10.39 | 10.17 | 9.80 |
| 9 | 8.83 | 9.34 | 9.82 | 10.23 | 10.46 | 10.63 | 10.68 | 10.82 | 11.48 | 12.44 | 12.11 | 11.94 | 11.67 | 11.25 |
| 10 | 9.59 | 10.23 | 10.76 | 11.29 | 11.64 | 11.86 | 11.94 | 12.11 | 12.85 | 13.92 | 13.56 | 13.38 | 13.12 | 12.67 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.560 |
| SC2 | 0 | 8 | 9.486 |
| SC3 | -18 | 7 | 7.914 |
| SC4 | -25 | 6 | 6.403 |
| SC5 | -34 | 6 | 6.096 |
| A | 2107 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 455 mm |
| E2 | 437.5 mm |
| E | 1785 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.