EA-250AC8-C09 C
15.26 kW
Defrost: None
Product code: EA-435AC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,076 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 60.9 m² |
| Inner volume | 13.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 88 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-435AC4-C01 C | None |
|---|---|
| EA-435AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.67 | 5.61 | 5.59 | 5.59 | 5.56 | 5.52 | 5.47 | 5.61 | 5.95 | 6.44 | 6.31 | 6.26 | 6.19 | 6.10 |
| 5 | 7.58 | 7.61 | 7.64 | 7.68 | 7.66 | 7.60 | 7.51 | 7.64 | 8.12 | 8.79 | 8.58 | 8.51 | 8.42 | 8.30 |
| 6 | 9.52 | 9.68 | 9.83 | 9.93 | 9.96 | 9.92 | 9.81 | 9.92 | 10.52 | 11.36 | 11.02 | 10.91 | 10.75 | 10.52 |
| 7 | 11.27 | 11.59 | 11.91 | 12.19 | 12.36 | 12.38 | 12.28 | 12.37 | 13.11 | 14.16 | 13.69 | 13.53 | 13.28 | 12.90 |
| 8 | 12.79 | 13.28 | 13.74 | 14.09 | 14.35 | 14.48 | 14.51 | 14.67 | 15.58 | 16.91 | 16.47 | 16.31 | 16.04 | 15.53 |
| 9 | 14.20 | 14.83 | 15.45 | 16.01 | 16.37 | 16.57 | 16.63 | 16.81 | 17.84 | 19.36 | 18.87 | 18.66 | 18.36 | 17.85 |
| 10 | 15.42 | 16.35 | 17.17 | 17.89 | 18.36 | 18.64 | 18.76 | 18.98 | 20.15 | 21.85 | 21.31 | 21.07 | 20.71 | 20.11 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 21.306 |
| SC2 | 0 | 8 | 14.674 |
| SC3 | -18 | 7 | 12.270 |
| SC4 | -25 | 6 | 9.830 |
| SC5 | -34 | 6 | 9.571 |
| A | 2357 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2357 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.