EA-245AG7-C01 C
19.59 kW
Defrost: None
Product code: EA-440AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,165 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 53.4 m² |
| Inner volume | 23.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 121 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | B |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-440AE10-C01 C | None |
|---|---|
| EA-440AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.21 | 7.25 | 7.30 | 7.35 | 7.33 | 7.28 | 7.18 | 7.33 | 7.78 | 8.40 | 8.17 | 8.08 | 7.96 | 7.77 |
| 5 | 9.41 | 9.63 | 9.83 | 10.01 | 10.08 | 10.06 | 9.96 | 10.13 | 10.76 | 11.64 | 11.31 | 11.19 | 11.04 | 10.81 |
| 6 | 11.57 | 11.99 | 12.38 | 12.72 | 12.89 | 12.95 | 12.90 | 13.08 | 13.88 | 15.03 | 14.58 | 14.41 | 14.15 | 13.75 |
| 7 | 13.50 | 14.15 | 14.75 | 15.30 | 15.67 | 15.89 | 15.92 | 16.08 | 17.07 | 18.52 | 17.99 | 17.78 | 17.46 | 16.92 |
| 8 | 15.16 | 16.05 | 16.88 | 17.53 | 18.05 | 18.38 | 18.54 | 18.84 | 20.03 | 21.78 | 21.29 | 21.07 | 20.74 | 20.18 |
| 9 | 16.68 | 17.84 | 18.79 | 19.75 | 20.43 | 20.88 | 21.13 | 21.49 | 22.85 | 24.85 | 24.31 | 24.06 | 23.68 | 23.02 |
| 10 | 18.06 | 19.39 | 20.71 | 21.88 | 22.76 | 23.36 | 23.70 | 24.15 | 25.68 | 27.93 | 27.36 | 27.08 | 26.65 | 25.88 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 27.360 |
| SC2 | 0 | 8 | 18.841 |
| SC3 | -18 | 7 | 15.467 |
| SC4 | -25 | 6 | 12.384 |
| SC5 | -34 | 6 | 11.674 |
| A | 2567 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2235 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 2567 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.