EA-445AC8-C01 C
23.46 kW
Defrost: None
Product code: EA-440AE6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 11,146 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 84.4 m² |
| Inner volume | 24.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 125 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-440AE6-C01 C | None |
|---|---|
| EA-440AE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.04 | 8.96 | 8.94 | 8.96 | 8.92 | 8.85 | 8.75 | 9.01 | 9.62 | 10.44 | 10.23 | 10.15 | 10.03 | 9.86 |
| 5 | 11.90 | 11.94 | 12.02 | 12.10 | 12.09 | 12.01 | 11.86 | 12.09 | 12.85 | 13.92 | 13.55 | 13.43 | 13.28 | 13.07 |
| 6 | 14.78 | 14.93 | 15.16 | 15.38 | 15.44 | 15.38 | 15.21 | 15.40 | 16.33 | 17.66 | 17.10 | 16.90 | 16.61 | 16.17 |
| 7 | 17.47 | 17.92 | 18.35 | 18.72 | 18.90 | 18.88 | 18.73 | 18.89 | 20.00 | 21.63 | 20.90 | 20.62 | 20.20 | 19.53 |
| 8 | 19.91 | 20.60 | 21.27 | 21.87 | 22.24 | 22.42 | 22.32 | 22.49 | 23.78 | 25.72 | 24.88 | 24.53 | 24.00 | 23.13 |
| 9 | 22.11 | 23.08 | 23.98 | 24.70 | 25.20 | 25.47 | 25.52 | 25.81 | 27.38 | 29.66 | 28.86 | 28.51 | 27.90 | 26.84 |
| 10 | 24.16 | 25.44 | 26.50 | 27.53 | 28.19 | 28.58 | 28.69 | 29.03 | 30.78 | 33.34 | 32.46 | 32.05 | 31.43 | 30.35 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 32.462 |
| SC2 | 0 | 8 | 22.487 |
| SC3 | -18 | 7 | 18.816 |
| SC4 | -25 | 6 | 15.163 |
| SC5 | -34 | 6 | 14.839 |
| A | 2567 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2235 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2567 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.