EA-263FE7-C19 C
34.96 kW
Defrost: None
Product code: EA-445AG10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 18,372 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 97.7 m² |
| Inner volume | 45.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 204 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-445AG10-C01 C | None |
|---|---|
| EA-445AG10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.13 | 13.10 | 13.12 | 13.15 | 13.09 | 12.96 | 12.78 | 13.09 | 13.94 | 15.09 | 14.69 | 14.54 | 14.33 | 14.01 |
| 5 | 17.22 | 17.44 | 17.67 | 17.87 | 17.91 | 17.82 | 17.60 | 17.89 | 19.00 | 20.56 | 19.95 | 19.76 | 19.49 | 19.12 |
| 6 | 21.27 | 21.70 | 22.22 | 22.68 | 22.90 | 22.90 | 22.72 | 22.98 | 24.37 | 26.36 | 25.51 | 25.20 | 24.73 | 24.01 |
| 7 | 24.97 | 25.90 | 26.77 | 27.53 | 27.96 | 28.08 | 27.98 | 28.26 | 29.95 | 32.43 | 31.39 | 30.98 | 30.36 | 29.35 |
| 8 | 28.31 | 29.62 | 30.86 | 31.97 | 32.70 | 33.12 | 33.17 | 33.58 | 35.61 | 38.55 | 37.41 | 36.92 | 36.17 | 34.91 |
| 9 | 31.29 | 33.05 | 34.68 | 35.97 | 36.94 | 37.55 | 37.82 | 38.35 | 40.73 | 44.20 | 43.13 | 42.64 | 41.88 | 40.56 |
| 10 | 34.04 | 36.29 | 38.15 | 39.94 | 41.24 | 42.05 | 42.46 | 43.10 | 45.78 | 49.68 | 48.53 | 47.97 | 47.12 | 45.54 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 48.526 |
| SC2 | 0 | 8 | 33.582 |
| SC3 | -18 | 7 | 27.738 |
| SC4 | -25 | 6 | 22.222 |
| SC5 | -34 | 6 | 21.404 |
| A | 3167 mm |
|---|---|
| B | 690 mm |
| C | 645 mm |
| F | 495 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2835 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3167 mm |
|---|---|
| Width | 690 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.