EA-463ED10-C06 C
41.15 kW
Defrost: None
Product code: EA-450AE8-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 26,012 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 115.2 m² |
| Inner volume | 44.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 212 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 2,840 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 84.0 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø54 |
| EA-450AE8-C09 C | None |
|---|---|
| EA-450AE8-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.14 | 14.90 | 14.75 | 14.67 | 14.52 | 14.33 | 14.11 | 14.32 | 15.13 | 16.31 | 15.86 | 15.69 | 15.46 | 15.12 |
| 5 | 20.36 | 20.33 | 20.36 | 20.40 | 20.29 | 20.07 | 19.78 | 19.98 | 21.18 | 22.86 | 22.19 | 21.96 | 21.64 | 21.18 |
| 6 | 25.61 | 25.81 | 26.14 | 26.44 | 26.49 | 26.34 | 26.03 | 26.21 | 27.76 | 29.94 | 28.97 | 28.62 | 28.14 | 27.42 |
| 7 | 30.53 | 31.28 | 31.99 | 32.62 | 32.90 | 32.86 | 32.63 | 32.82 | 34.74 | 37.51 | 36.27 | 35.80 | 35.11 | 34.03 |
| 8 | 34.88 | 36.07 | 37.21 | 38.26 | 38.94 | 39.31 | 39.42 | 39.61 | 41.94 | 45.38 | 43.96 | 43.40 | 42.56 | 41.20 |
| 9 | 38.83 | 40.52 | 42.09 | 43.35 | 44.31 | 44.88 | 45.12 | 45.61 | 48.43 | 52.55 | 51.30 | 50.76 | 49.95 | 48.60 |
| 10 | 42.51 | 44.55 | 46.60 | 48.45 | 49.69 | 50.49 | 50.88 | 51.50 | 54.68 | 59.34 | 57.98 | 57.37 | 56.45 | 54.89 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 57.979 |
| SC2 | 0 | 8 | 39.610 |
| SC3 | -18 | 7 | 32.766 |
| SC4 | -25 | 6 | 26.142 |
| SC5 | -34 | 6 | 25.708 |
| A | 3787 mm |
|---|---|
| B | 640 mm |
| C | 715 mm |
| F | 560 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 3435 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø54 |
| Length | 3787 mm |
|---|---|
| Width | 640 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.