EA-450AG7-C10 C
50.26 kW
Defrost: None
Product code: EA-450BE7-C10 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 29,379 m³/h |
|---|---|
| Air throw | 24 m |
| External surface | 270.4 m² |
| Inner volume | 80.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 328 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 2,760 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-450BE7-C10 C | None |
|---|---|
| EA-450BE7-C10 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 20.48 | 20.09 | 19.93 | 19.92 | 19.88 | 19.81 | 19.74 | 19.94 | 21.19 | 22.96 | 22.51 | 22.34 | 22.11 | 21.75 |
| 5 | 26.89 | 26.56 | 26.45 | 26.48 | 26.43 | 26.31 | 26.17 | 26.31 | 27.91 | 30.21 | 29.52 | 29.28 | 28.93 | 28.42 |
| 6 | 33.50 | 33.31 | 33.28 | 33.44 | 33.43 | 33.31 | 33.11 | 33.20 | 35.18 | 38.04 | 37.06 | 36.70 | 36.19 | 35.41 |
| 7 | 39.93 | 40.05 | 40.33 | 40.67 | 40.77 | 40.66 | 40.45 | 40.51 | 42.89 | 46.36 | 45.09 | 44.62 | 43.92 | 42.84 |
| 8 | 46.14 | 46.71 | 47.34 | 47.98 | 48.26 | 48.28 | 48.10 | 48.09 | 50.91 | 55.04 | 53.50 | 52.91 | 52.03 | 50.63 |
| 9 | 52.09 | 53.20 | 54.11 | 55.14 | 55.70 | 55.91 | 55.83 | 55.93 | 59.22 | 64.02 | 62.26 | 61.54 | 60.50 | 58.80 |
| 10 | 57.36 | 59.05 | 60.67 | 62.21 | 63.19 | 63.62 | 63.70 | 63.90 | 67.68 | 73.19 | 71.24 | 70.43 | 69.23 | 67.25 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 18.07 | 17.72 | 17.59 | 17.61 | 17.59 | 17.56 | 17.52 | 17.76 | 18.88 | 20.50 | 20.14 | 20.02 | 19.83 | 19.54 |
| 5 | 23.61 | 23.26 | 23.14 | 23.18 | 23.14 | 23.07 | 22.96 | 23.15 | 24.58 | 26.64 | 26.06 | 25.86 | 25.57 | 25.14 |
| 6 | 29.24 | 28.99 | 28.96 | 29.06 | 29.05 | 28.95 | 28.79 | 28.93 | 30.67 | 33.20 | 32.38 | 32.07 | 31.64 | 30.98 |
| 7 | 34.96 | 34.86 | 34.96 | 35.15 | 35.21 | 35.13 | 34.94 | 35.03 | 37.10 | 40.13 | 39.05 | 38.64 | 38.05 | 37.12 |
| 8 | 40.48 | 40.66 | 40.99 | 41.40 | 41.56 | 41.50 | 41.32 | 41.38 | 43.81 | 47.37 | 46.04 | 45.53 | 44.77 | 43.55 |
| 9 | 45.82 | 46.37 | 47.00 | 47.67 | 47.99 | 48.02 | 47.87 | 47.93 | 50.73 | 54.80 | 53.27 | 52.64 | 51.72 | 50.22 |
| 10 | 50.93 | 51.93 | 52.94 | 53.80 | 54.32 | 54.52 | 54.44 | 54.57 | 57.77 | 62.43 | 60.70 | 59.98 | 58.92 | 57.15 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 71.243 | 60.704 |
| SC2 | 0 | 8 | 48.092 | 41.380 |
| SC3 | -18 | 7 | 40.734 | 35.193 |
| SC4 | -25 | 6 | 33.281 | 28.955 |
| SC5 | -34 | 6 | 33.492 | 29.216 |
| A | 4427 mm |
|---|---|
| B | 740 mm |
| C | 875 mm |
| F | 660 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 4035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 4427 mm |
|---|---|
| Width | 740 mm |
| Height | 875 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.