EA-363EG4-C01 C
51.48 kW
Defrost: None
Product code: EA-463EE7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 31,843 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 270.4 m² |
| Inner volume | 81.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 380 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 2,400 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 80.4 dB(A) |
| Energy class | C |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-463EE7-C01 C | None |
|---|---|
| EA-463EE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 20.23 | 20.05 | 20.01 | 20.06 | 20.02 | 19.93 | 19.79 | 20.20 | 21.47 | 23.26 | 22.78 | 22.60 | 22.35 | 21.98 |
| 5 | 26.55 | 26.48 | 26.61 | 26.79 | 26.79 | 26.66 | 26.45 | 26.82 | 28.49 | 30.85 | 30.12 | 29.87 | 29.52 | 29.01 |
| 6 | 32.68 | 33.08 | 33.49 | 33.89 | 34.01 | 33.88 | 33.63 | 33.94 | 36.00 | 38.94 | 37.87 | 37.49 | 36.94 | 36.10 |
| 7 | 38.57 | 39.49 | 40.34 | 41.08 | 41.42 | 41.36 | 41.13 | 41.42 | 43.88 | 47.45 | 46.07 | 45.54 | 44.76 | 43.53 |
| 8 | 44.10 | 45.46 | 46.85 | 48.06 | 48.74 | 48.98 | 48.86 | 49.17 | 52.09 | 56.36 | 54.68 | 54.02 | 53.02 | 51.42 |
| 9 | 48.86 | 50.96 | 52.90 | 54.65 | 55.78 | 56.44 | 56.69 | 57.08 | 60.48 | 65.46 | 63.58 | 62.79 | 61.61 | 59.67 |
| 10 | 53.30 | 56.07 | 58.61 | 60.86 | 62.32 | 63.23 | 63.63 | 64.31 | 68.25 | 74.03 | 72.26 | 71.49 | 70.33 | 68.09 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 72.264 |
| SC2 | 0 | 8 | 49.166 |
| SC3 | -18 | 7 | 41.263 |
| SC4 | -25 | 6 | 33.491 |
| SC5 | -34 | 6 | 32.814 |
| A | 3615 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 3235 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 3615 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.