EA-235AE6-C01 C
8.67 kW
Defrost: None
Product code: EA-530AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,790 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 23.9 m² |
| Inner volume | 11.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 70 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 310 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.2 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-530AC10-C01 C | None |
|---|---|
| EA-530AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.15 | 3.14 | 3.13 | 3.14 | 3.12 | 3.10 | 3.06 | 3.11 | 3.29 | 3.55 | 3.45 | 3.42 | 3.37 | 3.29 |
| 5 | 4.17 | 4.21 | 4.26 | 4.31 | 4.32 | 4.30 | 4.26 | 4.31 | 4.57 | 4.94 | 4.81 | 4.76 | 4.70 | 4.60 |
| 6 | 5.16 | 5.28 | 5.40 | 5.51 | 5.56 | 5.58 | 5.55 | 5.61 | 5.95 | 6.43 | 6.25 | 6.18 | 6.09 | 5.94 |
| 7 | 6.12 | 6.34 | 6.54 | 6.72 | 6.84 | 6.88 | 6.89 | 6.96 | 7.38 | 7.99 | 7.78 | 7.69 | 7.57 | 7.36 |
| 8 | 6.98 | 7.29 | 7.58 | 7.85 | 8.05 | 8.17 | 8.23 | 8.32 | 8.83 | 9.59 | 9.35 | 9.25 | 9.10 | 8.86 |
| 9 | 7.73 | 8.15 | 8.54 | 8.86 | 9.11 | 9.29 | 9.40 | 9.54 | 10.15 | 11.04 | 10.83 | 10.74 | 10.59 | 10.35 |
| 10 | 8.43 | 8.96 | 9.41 | 9.86 | 10.19 | 10.42 | 10.57 | 10.74 | 11.43 | 12.44 | 12.21 | 12.11 | 11.95 | 11.68 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.214 |
| SC2 | 0 | 8 | 8.322 |
| SC3 | -18 | 7 | 6.777 |
| SC4 | -25 | 6 | 5.398 |
| SC5 | -34 | 6 | 5.190 |
| A | 2407 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 428 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.