EA-150AE7-C10 C
11.03 kW
Defrost: None
Product code: EA-530AC4-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,244 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 52.0 m² |
| Inner volume | 11.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 58 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| EA-530AC4-C05 C | None |
|---|---|
| EA-530AC4-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.20 | 4.28 | 4.35 | 4.42 | 4.45 | 4.45 | 4.42 | 4.56 | 4.87 | 5.30 | 5.21 | 5.18 | 5.14 | 5.08 |
| 5 | 5.41 | 5.59 | 5.73 | 5.87 | 5.95 | 5.97 | 5.93 | 6.07 | 6.46 | 7.01 | 6.83 | 6.77 | 6.69 | 6.58 |
| 6 | 6.52 | 6.84 | 7.11 | 7.36 | 7.51 | 7.56 | 7.54 | 7.66 | 8.14 | 8.82 | 8.57 | 8.48 | 8.34 | 8.12 |
| 7 | 7.48 | 7.91 | 8.30 | 8.61 | 8.84 | 8.98 | 9.03 | 9.18 | 9.76 | 10.62 | 10.36 | 10.25 | 10.09 | 9.79 |
| 8 | 8.34 | 8.92 | 9.39 | 9.85 | 10.17 | 10.37 | 10.45 | 10.62 | 11.29 | 12.27 | 11.97 | 11.84 | 11.64 | 11.30 |
| 9 | 9.13 | 9.79 | 10.46 | 11.05 | 11.47 | 11.73 | 11.87 | 12.07 | 12.83 | 13.94 | 13.61 | 13.45 | 13.22 | 12.80 |
| 10 | ≈ 9.79 | 10.66 | 11.48 | 12.21 | 12.74 | 13.09 | 13.28 | 13.53 | 14.38 | 15.62 | 15.27 | 15.09 | 14.82 | 14.34 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.270 |
| SC2 | 0 | 8 | 10.623 |
| SC3 | -18 | 7 | 8.712 |
| SC4 | -25 | 6 | 7.113 |
| SC5 | -34 | 6 | 6.596 |
| A | 2407 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 427.5 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.