EA-630BC8-C05 C
9.46 kW
Defrost: None
Product code: EA-530AC7-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,745 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 32.6 m² |
| Inner volume | 11.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 53 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-530AC7-C05 C | None |
|---|---|
| EA-530AC7-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.50 | 3.51 | 3.53 | 3.56 | 3.56 | 3.54 | 3.51 | 3.59 | 3.82 | 4.14 | 4.05 | 4.01 | 3.96 | 3.89 |
| 5 | 4.58 | 4.66 | 4.74 | 4.82 | 4.84 | 4.84 | 4.80 | 4.88 | 5.19 | 5.62 | 5.48 | 5.43 | 5.36 | 5.27 |
| 6 | 5.64 | 5.82 | 5.98 | 6.10 | 6.19 | 6.21 | 6.19 | 6.27 | 6.65 | 7.20 | 7.00 | 6.92 | 6.81 | 6.64 |
| 7 | 6.61 | 6.90 | 7.16 | 7.40 | 7.55 | 7.62 | 7.62 | 7.71 | 8.18 | 8.87 | 8.61 | 8.52 | 8.37 | 8.13 |
| 8 | 7.45 | 7.84 | 8.20 | 8.53 | 8.72 | 8.87 | 8.94 | 9.07 | 9.64 | 10.49 | 10.25 | 10.15 | 9.98 | 9.67 |
| 9 | 8.22 | 8.74 | 9.16 | 9.58 | 9.88 | 10.08 | 10.19 | 10.35 | 11.00 | 11.96 | 11.71 | 11.59 | 11.40 | 11.08 |
| 10 | 8.93 | 9.52 | 10.11 | 10.63 | 11.02 | 11.28 | 11.44 | 11.63 | 12.37 | 13.45 | 13.18 | 13.04 | 12.83 | 12.46 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.175 |
| SC2 | 0 | 8 | 9.071 |
| SC3 | -18 | 7 | 7.474 |
| SC4 | -25 | 6 | 5.976 |
| SC5 | -34 | 6 | 5.687 |
| A | 2407 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 427.5 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.