EA-335AG8-C01 C
13.60 kW
Defrost: None
Product code: EA-530AE4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,314 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 77.6 m² |
| Inner volume | 15.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 87 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 310 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.2 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-530AE4-C01 C | None |
|---|---|
| EA-530AE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.38 | 5.45 | 5.52 | 5.60 | 5.63 | 5.61 | 5.56 | 5.74 | 6.13 | 6.66 | 6.54 | 6.50 | 6.45 | 6.39 |
| 5 | 6.85 | 7.04 | 7.21 | 7.36 | 7.43 | 7.43 | 7.36 | 7.52 | 8.00 | 8.69 | 8.45 | 8.36 | 8.24 | 8.06 |
| 6 | 8.31 | 8.63 | 8.92 | 9.17 | 9.29 | 9.32 | 9.26 | 9.39 | 9.97 | 10.80 | 10.45 | 10.32 | 10.11 | 9.79 |
| 7 | 9.60 | 10.07 | 10.50 | 10.88 | 11.12 | 11.23 | 11.20 | 11.31 | 11.98 | 12.98 | 12.56 | 12.38 | 12.11 | 11.65 |
| 8 | 10.73 | 11.37 | 11.96 | 12.40 | 12.73 | 12.90 | 12.94 | 13.12 | 13.91 | 15.08 | 14.65 | 14.45 | 14.15 | 13.58 |
| 9 | 11.77 | 12.60 | 13.27 | 13.92 | 14.36 | 14.60 | 14.68 | 14.88 | 15.78 | 17.08 | 16.61 | 16.38 | 16.02 | 15.40 |
| 10 | 12.71 | 13.65 | 14.57 | 15.39 | 15.95 | 16.29 | 16.41 | 16.64 | 17.65 | 19.11 | 18.59 | 18.32 | 17.92 | 17.20 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.585 |
| SC2 | 0 | 8 | 13.115 |
| SC3 | -18 | 7 | 10.992 |
| SC4 | -25 | 6 | 8.921 |
| SC5 | -34 | 6 | 8.386 |
| A | 2407 mm |
|---|---|
| B | 573 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 428 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 2407 mm |
|---|---|
| Width | 573 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.