EA-163FC7-C19 C
11.78 kW
Defrost: None
Product code: EA-530AE6-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,845 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 55.8 m² |
| Inner volume | 15.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 68 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-530AE6-C05 C | None |
|---|---|
| EA-530AE6-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.66 | 4.68 | 4.72 | 4.76 | 4.77 | 4.75 | 4.71 | 4.86 | 5.18 | 5.64 | 5.53 | 5.50 | 5.46 | 5.42 |
| 5 | 5.99 | 6.09 | 6.19 | 6.29 | 6.32 | 6.31 | 6.25 | 6.38 | 6.78 | 7.36 | 7.16 | 7.09 | 6.99 | 6.84 |
| 6 | 7.32 | 7.47 | 7.67 | 7.84 | 7.92 | 7.93 | 7.88 | 7.98 | 8.47 | 9.18 | 8.89 | 8.78 | 8.61 | 8.36 |
| 7 | 8.53 | 8.85 | 9.15 | 9.40 | 9.55 | 9.59 | 9.54 | 9.64 | 10.22 | 11.07 | 10.72 | 10.58 | 10.36 | 10.01 |
| 8 | 9.65 | 10.09 | 10.51 | 10.88 | 11.12 | 11.24 | 11.23 | 11.32 | 11.99 | 12.97 | 12.59 | 12.42 | 12.16 | 11.72 |
| 9 | 10.64 | 11.23 | 11.78 | 12.21 | 12.52 | 12.70 | 12.75 | 12.92 | 13.70 | 14.84 | 14.46 | 14.28 | 13.99 | 13.47 |
| 10 | 11.56 | 12.31 | 12.94 | 13.54 | 13.95 | 14.19 | 14.28 | 14.46 | 15.34 | 16.62 | 16.21 | 16.01 | 15.70 | 15.15 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.206 |
| SC2 | 0 | 8 | 11.316 |
| SC3 | -18 | 7 | 9.476 |
| SC4 | -25 | 6 | 7.666 |
| SC5 | -34 | 6 | 7.364 |
| A | 2407 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 427.5 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2407 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.