EA-250AC7-C10 C
17.02 kW
Defrost: None
Product code: EA-535AC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,270 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 47.7 m² |
| Inner volume | 16.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 102 kg |
| Quantity | 5 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 825 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-535AC7-C01 C | None |
|---|---|
| EA-535AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.20 | 6.20 | 6.22 | 6.24 | 6.22 | 6.16 | 6.09 | 6.18 | 6.53 | 7.04 | 6.85 | 6.77 | 6.67 | 6.53 |
| 5 | 8.19 | 8.35 | 8.50 | 8.62 | 8.66 | 8.63 | 8.54 | 8.65 | 9.17 | 9.91 | 9.64 | 9.55 | 9.41 | 9.21 |
| 6 | 10.14 | 10.50 | 10.82 | 11.09 | 11.24 | 11.26 | 11.21 | 11.34 | 12.02 | 13.00 | 12.62 | 12.48 | 12.28 | 11.98 |
| 7 | 11.80 | 12.33 | 12.82 | 13.27 | 13.52 | 13.71 | 13.79 | 14.01 | 14.89 | 16.19 | 15.78 | 15.61 | 15.35 | 14.93 |
| 8 | 13.27 | 14.02 | 14.63 | 15.25 | 15.68 | 15.96 | 16.10 | 16.35 | 17.38 | 18.90 | 18.49 | 18.32 | 18.06 | 17.63 |
| 9 | 14.63 | 15.52 | 16.42 | 17.22 | 17.81 | 18.20 | 18.42 | 18.71 | 19.90 | 21.64 | 21.19 | 20.99 | 20.69 | 20.18 |
| 10 | 15.79 | 17.00 | 18.13 | 19.15 | 19.89 | 20.41 | 20.72 | 21.08 | 22.43 | 24.40 | 23.92 | 23.70 | 23.36 | 22.76 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 23.920 |
| SC2 | 0 | 8 | 16.346 |
| SC3 | -18 | 7 | 13.407 |
| SC4 | -25 | 6 | 10.816 |
| SC5 | -34 | 6 | 10.233 |
| A | 2857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |