EA-163EE4-C06 C
15.58 kW
Defrost: None
Product code: EA-535AC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,490 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 42.4 m² |
| Inner volume | 16.1 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 103 kg |
| Quantity | 5 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 825 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-535AC8-C01 C | None |
|---|---|
| EA-535AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.64 | 5.60 | 5.59 | 5.59 | 5.55 | 5.49 | 5.42 | 5.47 | 5.78 | 6.23 | 6.06 | 5.99 | 5.90 | 5.77 |
| 5 | 7.51 | 7.60 | 7.68 | 7.76 | 7.77 | 7.72 | 7.64 | 7.71 | 8.17 | 8.82 | 8.57 | 8.48 | 8.36 | 8.18 |
| 6 | 9.37 | 9.61 | 9.84 | 10.04 | 10.11 | 10.13 | 10.07 | 10.15 | 10.76 | 11.63 | 11.29 | 11.16 | 10.98 | 10.71 |
| 7 | 11.04 | 11.45 | 11.85 | 12.22 | 12.47 | 12.61 | 12.61 | 12.71 | 13.46 | 14.58 | 14.18 | 14.02 | 13.79 | 13.41 |
| 8 | 12.47 | 13.07 | 13.64 | 14.09 | 14.44 | 14.67 | 14.80 | 15.01 | 15.96 | 17.35 | 16.99 | 16.83 | 16.61 | 16.23 |
| 9 | 13.80 | 14.52 | 15.28 | 15.95 | 16.43 | 16.76 | 16.95 | 17.20 | 18.29 | 19.90 | 19.49 | 19.31 | 19.04 | 18.59 |
| 10 | 15.02 | 15.96 | 16.91 | 17.77 | 18.40 | 18.83 | 19.11 | 19.41 | 20.64 | 22.47 | 22.03 | 21.82 | 21.52 | 20.99 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 22.026 |
| SC2 | 0 | 8 | 15.008 |
| SC3 | -18 | 7 | 12.331 |
| SC4 | -25 | 6 | 9.839 |
| SC5 | -34 | 6 | 9.433 |
| A | 2857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |