EA-263EE7-C06 C
26.17 kW
Defrost: None
Product code: EA-540AC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,023 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 97.6 m² |
| Inner volume | 20.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 133 kg |
| Quantity | 5 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-540AC4-C01 C | None |
|---|---|
| EA-540AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.82 | 9.69 | 9.62 | 9.60 | 9.55 | 9.47 | 9.38 | 9.61 | 10.18 | 11.02 | 10.79 | 10.70 | 10.59 | 10.42 |
| 5 | 13.17 | 13.15 | 13.17 | 13.20 | 13.14 | 13.02 | 12.85 | 13.08 | 13.89 | 15.03 | 14.66 | 14.54 | 14.37 | 14.14 |
| 6 | 16.59 | 16.78 | 16.96 | 17.09 | 17.10 | 16.98 | 16.76 | 16.96 | 17.98 | 19.42 | 18.83 | 18.63 | 18.35 | 17.96 |
| 7 | 19.71 | 20.16 | 20.62 | 21.05 | 21.27 | 21.21 | 20.97 | 21.14 | 22.38 | 24.17 | 23.36 | 23.06 | 22.63 | 21.96 |
| 8 | 22.41 | 23.14 | 23.83 | 24.37 | 24.74 | 24.91 | 24.90 | 25.18 | 26.72 | 28.99 | 28.21 | 27.83 | 27.27 | 26.38 |
| 9 | 24.97 | 25.91 | 26.86 | 27.71 | 28.25 | 28.52 | 28.56 | 28.85 | 30.60 | 33.18 | 32.29 | 31.92 | 31.38 | 30.47 |
| 10 | 27.24 | 28.63 | 29.90 | 31.02 | 31.72 | 32.12 | 32.23 | 32.57 | 34.55 | 37.44 | 36.46 | 36.02 | 35.38 | 34.30 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 36.456 |
| SC2 | 0 | 8 | 25.181 |
| SC3 | -18 | 7 | 21.164 |
| SC4 | -25 | 6 | 16.959 |
| SC5 | -34 | 6 | 16.658 |
| A | 3117 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2785 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 3117 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.