EA-550AC6-C10 C
42.52 kW
Defrost: None
Product code: EA-550AE10-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 32,604 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 111.7 m² |
| Inner volume | 52.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 248 kg |
| Quantity | 5 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 3,550 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø54 |
| EA-550AE10-C09 C | None |
|---|---|
| EA-550AE10-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.20 | 15.01 | 14.89 | 14.81 | 14.64 | 14.43 | 14.18 | 14.33 | 15.12 | 16.26 | 15.76 | 15.58 | 15.32 | 14.94 |
| 5 | 20.45 | 20.54 | 20.65 | 20.74 | 20.67 | 20.46 | 20.15 | 20.35 | 21.57 | 23.25 | 22.53 | 22.29 | 21.94 | 21.38 |
| 6 | 25.67 | 26.15 | 26.52 | 26.93 | 27.07 | 26.98 | 26.71 | 26.92 | 28.51 | 30.76 | 29.76 | 29.40 | 28.90 | 28.15 |
| 7 | 30.50 | 31.50 | 32.42 | 33.22 | 33.64 | 33.71 | 33.57 | 33.82 | 35.83 | 38.72 | 37.50 | 37.03 | 36.33 | 35.23 |
| 8 | 34.76 | 36.22 | 37.59 | 38.84 | 39.68 | 40.09 | 40.31 | 40.84 | 43.33 | 46.92 | 45.56 | 45.02 | 44.20 | 42.85 |
| 9 | 38.58 | 40.59 | 42.45 | 43.92 | 45.09 | 45.84 | 46.23 | 46.84 | 49.77 | 54.09 | 52.89 | 52.38 | 51.62 | 50.31 |
| 10 | 42.12 | 44.51 | 46.88 | 49.02 | 50.55 | 51.54 | 52.13 | 52.88 | 56.21 | 61.09 | 59.82 | 59.24 | 58.37 | 56.88 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 59.819 |
| SC2 | 0 | 8 | 40.836 |
| SC3 | -18 | 7 | 33.428 |
| SC4 | -25 | 6 | 26.519 |
| SC5 | -34 | 6 | 25.808 |
| A | 4387 mm |
|---|---|
| B | 640 mm |
| C | 715 mm |
| F | 560 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø54 |
| Length | 4387 mm |
|---|---|
| Width | 640 mm |
| Height | 715 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.