EA-291AG7-C04 C
104.65 kW
Defrost: None
Product code: EA-563FE4-C19 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 55,394 m³/h |
|---|---|
| Air throw | 33 m |
| External surface | 626.5 m² |
| Inner volume | 127.0 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 582 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FE4-C19 C | None |
|---|---|
| EA-563FE4-C19 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 40.72 | 41.01 | 41.29 | 41.75 | 41.93 | 41.94 | 41.82 | 42.42 | 45.11 | 48.93 | 47.98 | 47.62 | 47.10 | 46.32 |
| 5 | 52.26 | 53.45 | 54.53 | 55.49 | 55.94 | 56.04 | 55.83 | 56.38 | 59.85 | 64.79 | 63.29 | 62.76 | 62.02 | 60.90 |
| 6 | 63.18 | 65.22 | 67.35 | 69.18 | 70.23 | 70.69 | 70.68 | 71.26 | 75.60 | 81.88 | 79.82 | 79.04 | 77.89 | 76.13 |
| 7 | 72.54 | 76.04 | 79.25 | 82.11 | 84.04 | 85.26 | 85.89 | 86.85 | 92.15 | 99.86 | 97.34 | 96.35 | 94.86 | 92.45 |
| 8 | 81.00 | 85.81 | 90.20 | 94.07 | 96.75 | 98.47 | 99.43 | 100.61 | 106.91 | 116.17 | 113.71 | 112.70 | 111.17 | 108.61 |
| 9 | 88.75 | 94.98 | 100.69 | 105.72 | 109.29 | 111.61 | 112.99 | 114.45 | 121.64 | 132.18 | 129.43 | 128.25 | 126.45 | 123.41 |
| 10 | ≈ 95.78 | 103.54 | 110.69 | 117.02 | 121.54 | 124.65 | 126.54 | 128.36 | 136.46 | 148.32 | 145.34 | 144.00 | 141.95 | 138.47 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 35.68 | 35.76 | 36.00 | 36.34 | 36.49 | 36.49 | 36.40 | 37.05 | 39.43 | 42.82 | 42.07 | 41.81 | 41.46 | 40.86 |
| 5 | 45.99 | 46.58 | 47.22 | 47.86 | 48.09 | 48.13 | 47.97 | 48.55 | 51.57 | 55.93 | 54.67 | 54.23 | 53.60 | 52.67 |
| 6 | 55.80 | 57.23 | 58.55 | 59.72 | 60.33 | 60.50 | 60.23 | 60.73 | 64.43 | 69.81 | 68.04 | 67.38 | 66.41 | 64.90 |
| 7 | 65.03 | 67.17 | 69.39 | 71.33 | 72.48 | 72.99 | 72.99 | 73.54 | 77.97 | 84.46 | 82.21 | 81.33 | 80.00 | 77.74 |
| 8 | 72.95 | 76.35 | 79.49 | 82.31 | 84.18 | 85.33 | 85.85 | 86.68 | 91.92 | 99.59 | 96.94 | 95.85 | 94.08 | 91.09 |
| 9 | 80.28 | 84.82 | 88.97 | 92.64 | 95.15 | 96.67 | 97.47 | 98.56 | 104.66 | 113.59 | 111.05 | 109.85 | 107.98 | 104.75 |
| 10 | 87.02 | 92.79 | 98.08 | 102.72 | 105.92 | 107.99 | 109.12 | 110.42 | 117.27 | 127.27 | 124.43 | 123.02 | 120.85 | 117.01 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 145.339 | 124.427 |
| SC2 | 0 | 8 | 100.613 | 86.678 |
| SC3 | -18 | 7 | 82.985 | 71.870 |
| SC4 | -25 | 6 | 67.350 | 58.546 |
| SC5 | -34 | 6 | 63.790 | 56.181 |
| A | 5415 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.