EA-150AE8-C10 C
10.37 kW
Defrost: None
Product code: EA-630BC7-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,485 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 35.0 m² |
| Inner volume | 11.7 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 58 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 720 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-630BC7-C05 C | None |
|---|---|
| EA-630BC7-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.84 | 3.88 | 3.93 | 3.97 | 3.98 | 3.97 | 3.93 | 4.04 | 4.31 | 4.67 | 4.57 | 4.53 | 4.47 | 4.38 |
| 5 | 4.97 | 5.12 | 5.25 | 5.37 | 5.42 | 5.43 | 5.39 | 5.51 | 5.86 | 6.35 | 6.19 | 6.14 | 6.06 | 5.96 |
| 6 | 6.09 | 6.35 | 6.59 | 6.79 | 6.91 | 6.95 | 6.93 | 7.05 | 7.49 | 8.12 | 7.89 | 7.81 | 7.68 | 7.48 |
| 7 | 7.05 | 7.43 | 7.78 | 8.09 | 8.30 | 8.40 | 8.46 | 8.61 | 9.16 | 9.96 | 9.69 | 9.58 | 9.41 | 9.14 |
| 8 | 7.90 | 8.41 | 8.83 | 9.24 | 9.54 | 9.73 | 9.82 | 10.00 | 10.63 | 11.57 | 11.31 | 11.20 | 11.03 | 10.73 |
| 9 | 8.67 | 9.26 | 9.86 | 10.40 | 10.79 | 11.04 | 11.18 | 11.39 | 12.11 | 13.18 | 12.90 | 12.77 | 12.56 | 12.21 |
| 10 | ≈ 9.37 | 10.11 | 10.85 | 11.51 | 12.00 | 12.34 | 12.53 | 12.79 | 13.60 | 14.80 | 14.50 | 14.35 | 14.12 | 13.72 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.501 |
| SC2 | 0 | 8 | 9.995 |
| SC3 | -18 | 7 | 8.185 |
| SC4 | -25 | 6 | 6.587 |
| SC5 | -34 | 6 | 6.149 |
| A | 2557 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.