EA-150AE8-C09 C
10.20 kW
Defrost: None
Product code: EA-630BC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,584 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 31.1 m² |
| Inner volume | 11.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 77 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 72.3 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-630BC8-C01 C | None |
|---|---|
| EA-630BC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.69 | 3.72 | 3.75 | 3.78 | 3.78 | 3.75 | 3.72 | 3.79 | 4.02 | 4.34 | 4.23 | 4.19 | 4.13 | 4.04 |
| 5 | 4.83 | 4.95 | 5.06 | 5.16 | 5.20 | 5.20 | 5.17 | 5.24 | 5.57 | 6.03 | 5.87 | 5.82 | 5.75 | 5.64 |
| 6 | 5.95 | 6.18 | 6.39 | 6.58 | 6.67 | 6.72 | 6.72 | 6.80 | 7.22 | 7.83 | 7.61 | 7.54 | 7.42 | 7.24 |
| 7 | 6.93 | 7.28 | 7.60 | 7.89 | 8.10 | 8.23 | 8.28 | 8.41 | 8.93 | 9.69 | 9.45 | 9.35 | 9.21 | 8.98 |
| 8 | 7.78 | 8.25 | 8.70 | 9.04 | 9.33 | 9.52 | 9.64 | 9.80 | 10.43 | 11.35 | 11.13 | 11.04 | 10.90 | 10.65 |
| 9 | 8.56 | 9.09 | 9.68 | 10.19 | 10.57 | 10.83 | 11.00 | 11.19 | 11.91 | 12.97 | 12.73 | 12.63 | 12.46 | 12.18 |
| 10 | 9.26 | 9.96 | 10.67 | 11.30 | 11.78 | 12.12 | 12.34 | 12.59 | 13.40 | 14.60 | 14.35 | 14.23 | 14.05 | 13.72 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.350 |
| SC2 | 0 | 8 | 9.797 |
| SC3 | -18 | 7 | 7.984 |
| SC4 | -25 | 6 | 6.393 |
| SC5 | -34 | 6 | 6.004 |
| A | 2557 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2557 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.