EA-335AE6-C01 C
13.87 kW
Defrost: None
Product code: EA-630BE7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,594 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 52.1 m² |
| Inner volume | 16.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 88 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 73.8 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-630BE7-C01 C | None |
|---|---|
| EA-630BE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.28 | 5.34 | 5.40 | 5.47 | 5.48 | 5.46 | 5.40 | 5.55 | 5.91 | 6.41 | 6.28 | 6.24 | 6.18 | 6.08 |
| 5 | 6.79 | 6.98 | 7.15 | 7.30 | 7.38 | 7.38 | 7.32 | 7.45 | 7.92 | 8.59 | 8.35 | 8.27 | 8.15 | 7.98 |
| 6 | 8.28 | 8.61 | 8.92 | 9.18 | 9.31 | 9.37 | 9.33 | 9.47 | 10.04 | 10.89 | 10.56 | 10.42 | 10.23 | 9.91 |
| 7 | 9.59 | 10.08 | 10.53 | 10.94 | 11.20 | 11.36 | 11.36 | 11.52 | 12.21 | 13.25 | 12.84 | 12.66 | 12.40 | 11.97 |
| 8 | 10.73 | 11.40 | 12.01 | 12.48 | 12.86 | 13.08 | 13.17 | 13.38 | 14.22 | 15.43 | 15.03 | 14.85 | 14.57 | 14.09 |
| 9 | 11.78 | 12.63 | 13.33 | 14.03 | 14.51 | 14.83 | 14.97 | 15.22 | 16.17 | 17.54 | 17.10 | 16.89 | 16.56 | 15.99 |
| 10 | 12.73 | 13.69 | 14.66 | 15.51 | 16.14 | 16.55 | 16.76 | 17.06 | 18.12 | 19.66 | 19.19 | 18.95 | 18.57 | 17.91 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 19.188 |
| SC2 | 0 | 8 | 13.384 |
| SC3 | -18 | 7 | 11.058 |
| SC4 | -25 | 6 | 8.916 |
| SC5 | -34 | 6 | 8.359 |
| A | 2557 mm |
|---|---|
| B | 573 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2407 mm |
|---|---|
| Width | 573 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.