Skip to Content

Unit cooler ED-A-A-125AC6-B24 C

Unit cooler ED-A-A-125AC6-B24 C
Illustrative photo

Producer: Karyer · Line: ED-A A (Commercial Double Flow)

Product code: ED-A-A-125AC6-B24 C

Cooling capacity i
0.72 kW
Air flow
502 m³/h
Fin spacing
6.0 mm
Air throw
2 m
Fans
1 × ⌀250 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): ED-A — ED-A - commercial double-flow ceiling evaporator, aluminium casing
  • B
    Design type: A — Design type A
  • C
    Number of fans: 1 — Number of fans (one digit).
  • D
    Fan diameter: 25 — Ø250 mm
  • G
    Fin spacing: 6 — Fin spacing about 6 mm
  • H
    Generation code: B — Generation B
  • I
    Fan data: 24 — Ø250: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 502 m³/h
Air throw 2 m
External surface 2.4 m²
Inner volume 0.7 dm³
Fin spacing 6.0 mm
Fin materialAluminium
Net weight 6 kg
Fans
Quantity 1
Diameter 250 mm
Speed 1,300 rpm
Power 65 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 34.0 dB(A)
Sound power 54.7 dB(A)
Energy class E
Connections
Inlet Ø9,52
Outlet Ø9,52
Defrost
ED-A-A-125AC6-B24 C None
ED-A-A-125AC6-B24 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
0.692 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 0.26 0.26 0.26 0.27 0.27 0.26 0.26 0.27 0.28 0.31 0.30 0.30 0.29 0.29
5 0.35 0.35 0.36 0.36 0.36 0.36 0.36 0.36 0.39 0.42 0.41 0.40 0.40 0.39
6 0.43 0.44 0.45 0.46 0.47 0.47 0.46 0.47 0.50 0.54 0.52 0.51 0.50 0.49
7 0.50 0.53 0.54 0.56 0.57 0.58 0.57 0.58 0.61 0.67 0.64 0.64 0.62 0.60
8 0.57 0.61 0.63 0.66 0.68 0.68 0.69 0.69 0.73 0.80 0.77 0.76 0.75 0.72
9 0.64 0.68 0.71 0.75 0.77 0.78 0.79 0.80 0.85 0.92 0.90 0.89 0.87 0.84
10 0.70 0.74 0.79 0.83 0.86 0.88 0.89 0.90 0.96 1.04 1.02 1.01 0.99 0.96

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 1.018
SC2 0 8 0.692
SC3 -18 7 0.566
SC4 -25 6 0.452
SC5 -34 6 0.431

Dimensions

Dimension drawing of ED-A-A-125AC6-B24 C
Dimension drawing
Dimensions as drawn
A 570 mm
B 470 mm
C 150 mm
E 270 mm
D 300 mm
D IN 1 x Ø9,52
D OUT 1 x Ø9,52
Overall [mm]
Length 570 mm
Width 470 mm
Height 150 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.