ED-DP-335AC4-B22 C
10.81 kW
Defrost: None
Product code: ED-DP-335AE7-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,548 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 51.5 m² |
| Inner volume | 17.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 122 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 945 rpm |
| Power | 195 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | A |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-DP-335AE7-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.15 | 4.23 | 4.31 | 4.38 | 4.42 | 4.43 | 4.42 | 4.52 | 4.82 | 5.23 | 5.13 | 5.10 | 5.05 | 4.99 |
| 5 | 5.26 | 5.43 | 5.59 | 5.73 | 5.82 | 5.85 | 5.85 | 5.94 | 6.32 | 6.86 | 6.69 | 6.63 | 6.53 | 6.39 |
| 6 | 6.34 | 6.62 | 6.84 | 7.08 | 7.23 | 7.31 | 7.32 | 7.42 | 7.88 | 8.55 | 8.33 | 8.24 | 8.10 | 7.87 |
| 7 | 7.31 | 7.72 | 8.09 | 8.43 | 8.65 | 8.78 | 8.81 | 8.93 | 9.48 | 10.29 | 10.02 | 9.91 | 9.74 | 9.43 |
| 8 | 8.19 | 8.72 | 9.22 | 9.66 | 9.97 | 10.13 | 10.24 | 10.40 | 11.06 | 12.02 | 11.72 | 11.59 | 11.38 | 11.03 |
| 9 | 8.96 | 9.64 | 10.27 | 10.76 | 11.16 | 11.43 | 11.59 | 11.79 | 12.53 | 13.62 | 13.34 | 13.20 | 12.98 | 12.60 |
| 10 | ≈ 9.67 | 10.49 | 11.19 | 11.86 | 12.37 | 12.72 | 12.93 | 13.17 | 14.01 | 15.22 | 14.92 | 14.77 | 14.53 | 14.09 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.921 |
| SC2 | 0 | 8 | 10.402 |
| SC3 | -18 | 7 | 8.526 |
| SC4 | -25 | 6 | 6.843 |
| SC5 | -34 | 6 | 6.408 |
| A | 2148 mm |
|---|---|
| B | 900 mm |
| C | 325 mm |
| F | 940 mm |
| G | 410 mm |
| E1 | 1835 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2148 mm |
|---|---|
| Width | 900 mm |
| Height | 410 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.