Skip to Content

Unit cooler ED-DP-363AG7-B27 C

Unit cooler ED-DP-363AG7-B27 C
Illustrative photo

Producer: Karyer · Line: ED-DP (Processing Room)

Product code: ED-DP-363AG7-B27 C

Cooling capacity i
52.53 kW
Air flow
24,718 m³/h
Fin spacing
7.0 mm
Air throw
19 m
Fans
3 × ⌀630 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): ED-DP — ED-DP - double-flow processing-room unit cooler
  • B
    Number of fans: 3 — Number of fans (one digit).
  • C
    Fan diameter: 63 — Ø630 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: G — 8 tube rows
  • F
    Fin spacing: 7 — Fin spacing about 7 mm
  • G
    Generation code: B — Generation B
  • H
    Fan data: 27 — Ø630: 400V/3Ph/50Hz, 6-pole

Data

Evaporator
Air flow 24,718 m³/h
Air throw 19 m
External surface 323.0 m²
Inner volume 90.9 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 405 kg
Fans
Quantity 3
Diameter 630 mm
Speed 890 rpm
Power 1,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 78.3 dB(A)
Energy class B
Connections
Inlet Ø42
Outlet Ø66,7
Defrost
ED-DP-363AG7-B27 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
50.406 kW
Low speed (Y)
41.162 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 21.09 21.06 21.14 21.28 21.30 21.24 21.10 21.51 22.89 24.84 24.36 24.19 23.96 23.60
5 27.26 27.50 27.72 28.05 28.16 28.10 27.91 28.28 30.03 32.54 31.73 31.45 31.04 30.44
6 33.14 33.82 34.47 35.06 35.33 35.31 35.12 35.43 37.57 40.68 39.53 39.10 38.47 37.48
7 38.70 39.94 41.08 42.06 42.47 42.65 42.52 42.82 45.38 49.11 47.66 47.09 46.23 44.84
8 43.88 45.56 47.27 48.75 49.65 50.07 50.04 50.41 53.41 57.81 56.13 55.43 54.38 52.61
9 48.33 50.79 53.06 55.08 56.43 57.19 57.51 58.08 61.56 66.62 64.76 63.94 62.70 60.60
10 52.49 55.66 58.56 61.12 62.83 63.89 64.38 65.11 69.10 74.91 73.11 72.29 71.03 68.71

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 17.95 17.84 17.87 17.97 17.99 17.93 17.80 18.35 19.55 21.17 20.78 20.65 20.48 20.23
5 23.06 23.11 23.27 23.48 23.52 23.44 23.23 23.65 25.13 27.38 26.59 26.35 26.01 25.50
6 28.21 28.48 28.77 29.15 29.28 29.22 28.96 29.30 31.07 33.66 32.66 32.28 31.72 30.83
7 33.07 33.71 34.35 34.95 35.21 35.16 34.89 35.16 37.25 40.31 38.99 38.46 37.67 36.43
8 37.70 38.78 39.80 40.69 41.16 41.22 40.89 41.16 43.55 47.06 45.51 44.84 43.88 42.31
9 42.04 43.65 44.94 46.21 46.91 47.17 46.99 47.28 50.03 54.01 52.25 51.46 50.33 48.42
10 46.09 48.03 50.15 51.69 52.73 53.19 53.11 53.47 56.57 61.05 59.09 58.22 56.91 54.67

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 73.11459.094
SC2 0 8 50.40641.162
SC3 -18 7 42.18435.087
SC4 -25 6 34.46828.771
SC5 -34 6 33.32728.299

Dimensions

Dimension drawing of ED-DP-363AG7-B27 C
Dimension drawing
Dimensions as drawn
A 3968 mm
B 1700 mm
C 520 mm
F 1750 mm
G 660 mm
E1 3635 mm
E2 1218 mm
E3 1200 mm
D IN 1 x Ø42
D OUT 1 x Ø66,7
Overall [mm]
Length 3968 mm
Width 1700 mm
Height 660 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.