ED-DP-340AE7-B22 C
14.92 kW
Defrost: None
Product code: ED-DP-435AC4-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,287 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 73.0 m² |
| Inner volume | 15.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 147 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 945 rpm |
| Power | 260 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 66.0 dB(A) |
| Energy class | A |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-DP-435AC4-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.88 | 5.90 | 5.95 | 6.01 | 6.04 | 6.04 | 6.01 | 6.15 | 6.55 | 7.12 | 6.99 | 6.95 | 6.90 | 6.83 |
| 5 | 7.56 | 7.68 | 7.81 | 7.94 | 8.00 | 8.01 | 7.97 | 8.09 | 8.60 | 9.33 | 9.11 | 9.03 | 8.91 | 8.75 |
| 6 | 9.23 | 9.47 | 9.71 | 9.90 | 10.03 | 10.07 | 10.05 | 10.15 | 10.77 | 11.68 | 11.36 | 11.24 | 11.06 | 10.77 |
| 7 | 10.76 | 11.15 | 11.53 | 11.88 | 12.10 | 12.19 | 12.18 | 12.30 | 13.04 | 14.14 | 13.73 | 13.57 | 13.34 | 12.94 |
| 8 | 12.10 | 12.66 | 13.18 | 13.65 | 13.91 | 14.10 | 14.19 | 14.36 | 15.25 | 16.55 | 16.16 | 15.98 | 15.69 | 15.19 |
| 9 | 13.34 | 14.09 | 14.70 | 15.31 | 15.72 | 15.99 | 16.11 | 16.32 | 17.32 | 18.80 | 18.37 | 18.17 | 17.87 | 17.34 |
| 10 | 14.49 | 15.35 | 16.21 | 16.98 | 17.51 | 17.86 | 18.04 | 18.28 | 19.41 | 21.06 | 20.59 | 20.37 | 20.02 | 19.42 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.592 |
| SC2 | 0 | 8 | 14.360 |
| SC3 | -18 | 7 | 11.985 |
| SC4 | -25 | 6 | 9.705 |
| SC5 | -34 | 6 | 9.291 |
| A | 2748 mm |
|---|---|
| B | 900 mm |
| C | 325 mm |
| F | 940 mm |
| G | 410 mm |
| E1 | 2435 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2748 mm |
|---|---|
| Width | 900 mm |
| Height | 410 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.