Skip to Content

Unit cooler ED-DP-440AE4-B22 C

Unit cooler ED-DP-440AE4-B22 C
Illustrative photo

Producer: Karyer · Line: ED-DP (Processing Room)

Product code: ED-DP-440AE4-B22 C

Cooling capacity i
23.27 kW
Air flow
8,137 m³/h
Fin spacing
4.2 mm
Air throw
9 m
Fans
4 × ⌀400 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): ED-DP — ED-DP - double-flow processing-room unit cooler
  • B
    Number of fans: 4 — Number of fans (one digit).
  • C
    Fan diameter: 40 — Ø400 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: E — 6 tube rows
  • F
    Fin spacing: 4 — Fin spacing about 4 mm
  • G
    Generation code: B — Generation B
  • H
    Fan data: 22 — Ø350: 230V/1Ph/50Hz, 6-pole; Ø400: 230V/1Ph/50Hz, 6-pole

Data

Evaporator
Air flow 8,137 m³/h
Air throw 9 m
External surface 146.1 m²
Inner volume 31.7 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 190 kg
Fans
Quantity 4
Diameter 400 mm
Speed 870 rpm
Power 480 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 49.0 dB(A)
Sound power 71.0 dB(A)
Energy class B
Connections
Inlet Ø35
Outlet Ø42
Defrost
ED-DP-440AE4-B22 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
22.465 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 9.36 9.58 9.80 10.01 10.12 10.15 10.11 10.40 11.09 12.08 11.84 11.76 11.65 11.51
5 11.69 12.12 12.52 12.87 13.08 13.16 13.11 13.37 14.21 15.45 15.03 14.87 14.63 14.23
6 13.96 14.62 15.23 15.76 16.05 16.21 16.19 16.43 17.44 18.93 18.36 18.12 17.75 17.14
7 15.98 16.90 17.75 18.50 18.99 19.27 19.30 19.50 20.68 22.42 21.74 21.44 20.97 20.16
8 17.76 18.97 20.08 20.94 21.61 22.00 22.15 22.47 23.84 25.83 25.13 24.78 24.25 23.26
9 19.37 20.90 22.15 23.38 24.25 24.78 25.01 25.37 26.91 29.15 28.37 27.98 27.36 26.27
10 ≈ 20.84 22.53 24.22 25.73 26.83 27.51 27.85 28.27 30.00 32.49 31.63 31.20 30.50 29.26

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 31.634
SC2 0 8 22.465
SC3 -18 7 18.722
SC4 -25 6 15.228
SC5 -34 6 14.118

Dimensions

Dimension drawing of ED-DP-440AE4-B22 C
Dimension drawing
Dimensions as drawn
A 2748 mm
B 1050 mm
C 435 mm
F 1090 mm
G 570 mm
E1 2435 mm
E2 618 mm
E3 600 mm
D IN 1 x Ø35
D OUT 1 x Ø42
Overall [mm]
Length 2748 mm
Width 1050 mm
Height 570 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.