ED-DP-263AE4-B27 C
35.50 kW
Defrost: None
Product code: ED-DP-445AE4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,694 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 194.8 m² |
| Inner volume | 42.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 245 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 760 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | B |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| ED-DP-445AE4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.80 | 14.21 | 14.60 | 14.96 | 15.16 | 15.23 | 15.18 | 15.59 | 16.62 | 18.09 | 17.73 | 17.62 | 17.46 | 17.26 |
| 5 | 17.34 | 18.07 | 18.76 | 19.29 | 19.67 | 19.84 | 19.82 | 20.19 | 21.46 | 23.33 | 22.72 | 22.49 | 22.14 | 21.58 |
| 6 | 20.50 | 21.65 | 22.71 | 23.63 | 24.23 | 24.54 | 24.55 | 24.93 | 26.42 | 28.71 | 27.92 | 27.59 | 27.10 | 26.26 |
| 7 | 23.29 | 24.84 | 26.27 | 27.36 | 28.23 | 28.76 | 28.97 | 29.44 | 31.28 | 33.98 | 33.14 | 32.77 | 32.19 | 31.10 |
| 8 | 25.79 | 27.80 | 29.43 | 31.06 | 32.23 | 32.94 | 33.29 | 33.83 | 35.94 | 39.01 | 38.08 | 37.64 | 36.94 | 35.70 |
| 9 | ≈ 28.05 | 30.31 | 32.58 | 34.63 | 36.12 | 37.08 | 37.59 | 38.22 | 40.61 | 44.08 | 43.05 | 42.54 | 41.73 | 40.30 |
| 10 | 30.07 | 32.79 | 35.55 | 38.04 | 39.88 | 41.15 | 41.85 | 42.60 | 45.28 | 49.15 | 48.05 | 47.48 | 46.58 | 44.94 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 48.053 |
| SC2 | 0 | 8 | 33.827 |
| SC3 | -18 | 7 | 27.750 |
| SC4 | -25 | 6 | 22.705 |
| SC5 | -34 | 6 | 20.766 |
| A | 3548 mm |
|---|---|
| B | 1050 mm |
| C | 435 mm |
| F | 1090 mm |
| G | 570 mm |
| E1 | 3235 mm |
| E2 | 818 mm |
| E3 | 800 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 3548 mm |
|---|---|
| Width | 1050 mm |
| Height | 570 mm |
Our engineers answer with a selection for your conditions.