ED-130AC7-C25 C
1.82 kW
Defrost: None
Product code: ED-130AC7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,411 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 6.2 m² |
| Inner volume | 1.8 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 33 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.4 dB(A) |
| Energy class | B |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| ED-130AC7-C21 C | None |
|---|---|
| ED-130AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.75 | 0.72 | 0.71 | 0.71 | 0.70 | 0.70 | 0.70 | 0.71 | 0.75 | 0.81 | 0.79 | 0.79 | 0.78 | 0.77 |
| 5 | 1.01 | 0.99 | 0.97 | 0.97 | 0.96 | 0.95 | 0.94 | 0.95 | 1.01 | 1.09 | 1.07 | 1.06 | 1.05 | 1.03 |
| 6 | 1.29 | 1.27 | 1.26 | 1.25 | 1.25 | 1.23 | 1.22 | 1.22 | 1.30 | 1.40 | 1.36 | 1.35 | 1.33 | 1.30 |
| 7 | 1.58 | 1.56 | 1.56 | 1.56 | 1.55 | 1.54 | 1.52 | 1.52 | 1.61 | 1.74 | 1.69 | 1.67 | 1.64 | 1.60 |
| 8 | 1.86 | 1.86 | 1.86 | 1.87 | 1.87 | 1.86 | 1.85 | 1.85 | 1.95 | 2.11 | 2.04 | 2.01 | 1.97 | 1.92 |
| 9 | 2.14 | 2.15 | 2.17 | 2.19 | 2.20 | 2.20 | 2.18 | 2.18 | 2.31 | 2.49 | 2.41 | 2.38 | 2.33 | 2.26 |
| 10 | 2.41 | 2.44 | 2.48 | 2.52 | 2.53 | 2.54 | 2.53 | 2.53 | 2.68 | 2.89 | 2.80 | 2.76 | 2.71 | 2.62 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 2.800 |
| SC2 | 0 | 8 | 1.845 |
| SC3 | -18 | 7 | 1.556 |
| SC4 | -25 | 6 | 1.257 |
| SC5 | -34 | 6 | 1.287 |
| A | 848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 535 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.