ED-130AE7-C21 C
2.61 kW
Defrost: None
Product code: ED-130AE4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,020 m³/h |
|---|---|
| Air throw | 3 m |
| External surface | 19.0 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 36 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 120 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 41.0 dB(A) |
|---|---|
| Sound power | 62.0 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| ED-130AE4-C25 C | None |
|---|---|
| ED-130AE4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.15 | 1.16 | 1.17 | 1.19 | 1.19 | 1.19 | 1.19 | 1.22 | 1.31 | 1.42 | 1.40 | 1.39 | 1.38 | 1.37 |
| 5 | 1.46 | 1.49 | 1.51 | 1.54 | 1.55 | 1.55 | 1.54 | 1.57 | 1.67 | 1.82 | 1.77 | 1.75 | 1.73 | 1.69 |
| 6 | 1.76 | 1.81 | 1.85 | 1.90 | 1.92 | 1.92 | 1.91 | 1.94 | 2.05 | 2.23 | 2.16 | 2.13 | 2.09 | 2.03 |
| 7 | 2.06 | 2.12 | 2.19 | 2.25 | 2.29 | 2.30 | 2.29 | 2.31 | 2.45 | 2.65 | 2.57 | 2.53 | 2.48 | 2.39 |
| 8 | 2.33 | 2.44 | 2.53 | 2.62 | 2.67 | 2.68 | 2.67 | 2.70 | 2.86 | 3.09 | 2.99 | 2.95 | 2.88 | 2.77 |
| 9 | 2.58 | 2.72 | 2.85 | 2.97 | 3.04 | 3.07 | 3.06 | 3.09 | 3.27 | 3.53 | 3.42 | 3.37 | 3.29 | 3.16 |
| 10 | 2.80 | 2.98 | 3.14 | 3.29 | 3.38 | 3.43 | 3.44 | 3.47 | 3.68 | 3.98 | 3.85 | 3.79 | 3.70 | 3.56 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.853 |
| SC2 | 0 | 8 | 2.698 |
| SC3 | -18 | 7 | 2.271 |
| SC4 | -25 | 6 | 1.854 |
| SC5 | -34 | 6 | 1.774 |
| A | 848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 535 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.