ED-140AE7-C21 C
6.13 kW
Defrost: None
Product code: ED-140AC4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,301 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 24.3 m² |
| Inner volume | 5.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 54 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 160 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-140AC4-C21 C | None |
|---|---|
| ED-140AC4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.32 | 2.29 | 2.27 | 2.27 | 2.26 | 2.25 | 2.24 | 2.28 | 2.42 | 2.63 | 2.58 | 2.56 | 2.54 | 2.50 |
| 5 | 3.10 | 3.08 | 3.07 | 3.08 | 3.07 | 3.05 | 3.02 | 3.05 | 3.24 | 3.51 | 3.43 | 3.41 | 3.37 | 3.32 |
| 6 | 3.89 | 3.90 | 3.93 | 3.95 | 3.95 | 3.93 | 3.90 | 3.92 | 4.15 | 4.49 | 4.37 | 4.32 | 4.26 | 4.18 |
| 7 | 4.68 | 4.75 | 4.82 | 4.87 | 4.89 | 4.88 | 4.84 | 4.86 | 5.14 | 5.55 | 5.39 | 5.32 | 5.24 | 5.10 |
| 8 | 5.42 | 5.56 | 5.70 | 5.81 | 5.87 | 5.87 | 5.84 | 5.85 | 6.19 | 6.69 | 6.49 | 6.41 | 6.29 | 6.10 |
| 9 | 6.05 | 6.26 | 6.45 | 6.63 | 6.74 | 6.79 | 6.81 | 6.87 | 7.28 | 7.87 | 7.64 | 7.54 | 7.40 | 7.17 |
| 10 | 6.65 | 6.94 | 7.20 | 7.40 | 7.55 | 7.64 | 7.68 | 7.75 | 8.22 | 8.91 | 8.70 | 8.61 | 8.48 | 8.25 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.703 |
| SC2 | 0 | 8 | 5.853 |
| SC3 | -18 | 7 | 4.883 |
| SC4 | -25 | 6 | 3.926 |
| SC5 | -34 | 6 | 3.896 |
| A | 948 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 467 mm |
| E1 | 635 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 948 mm |
|---|---|
| Width | 1210 mm |
| Height | 467 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.