ED-230AC4-C21 C
5.80 kW
Defrost: None
Product code: ED-230AE4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,040 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 37.9 m² |
| Inner volume | 7.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 57 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-230AE4-C25 C | None |
|---|---|
| ED-230AE4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.41 | 2.42 | 2.43 | 2.46 | 2.47 | 2.46 | 2.44 | 2.52 | 2.69 | 2.92 | 2.87 | 2.85 | 2.83 | 2.80 |
| 5 | 3.08 | 3.11 | 3.15 | 3.19 | 3.21 | 3.20 | 3.17 | 3.23 | 3.44 | 3.73 | 3.63 | 3.59 | 3.54 | 3.46 |
| 6 | 3.72 | 3.79 | 3.86 | 3.94 | 3.97 | 3.97 | 3.94 | 3.98 | 4.22 | 4.58 | 4.43 | 4.38 | 4.29 | 4.15 |
| 7 | 4.36 | 4.48 | 4.58 | 4.68 | 4.74 | 4.75 | 4.72 | 4.76 | 5.04 | 5.45 | 5.27 | 5.20 | 5.08 | 4.89 |
| 8 | 4.94 | 5.12 | 5.29 | 5.44 | 5.52 | 5.54 | 5.51 | 5.55 | 5.87 | 6.34 | 6.14 | 6.04 | 5.90 | 5.67 |
| 9 | 5.49 | 5.73 | 5.96 | 6.16 | 6.28 | 6.33 | 6.31 | 6.35 | 6.72 | 7.25 | 7.02 | 6.91 | 6.73 | 6.46 |
| 10 | 5.98 | 6.29 | 6.58 | 6.83 | 6.97 | 7.05 | 7.07 | 7.13 | 7.55 | 8.15 | 7.90 | 7.78 | 7.58 | 7.27 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.900 |
| SC2 | 0 | 8 | 5.551 |
| SC3 | -18 | 7 | 4.712 |
| SC4 | -25 | 6 | 3.864 |
| SC5 | -34 | 6 | 3.740 |
| A | 1348 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 1035 mm |
| E2 | 518 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1348 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.