ED-440AE4-C21 C
29.73 kW
Defrost: None
Product code: ED-250AG7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,220 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 114.5 m² |
| Inner volume | 40.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 173 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 1,360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.1 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| ED-250AG7-C21 C | None |
|---|---|
| ED-250AG7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.50 | 11.47 | 11.49 | 11.53 | 11.51 | 11.44 | 11.34 | 11.55 | 12.29 | 13.32 | 13.04 | 12.94 | 12.80 | 12.56 |
| 5 | 15.00 | 15.14 | 15.31 | 15.48 | 15.52 | 15.47 | 15.33 | 15.52 | 16.47 | 17.83 | 17.34 | 17.17 | 16.94 | 16.61 |
| 6 | 18.36 | 18.77 | 19.17 | 19.53 | 19.70 | 19.71 | 19.59 | 19.75 | 20.93 | 22.64 | 21.96 | 21.70 | 21.32 | 20.73 |
| 7 | 21.67 | 22.38 | 23.05 | 23.63 | 23.92 | 24.05 | 23.98 | 24.15 | 25.58 | 27.68 | 26.84 | 26.50 | 26.00 | 25.17 |
| 8 | 24.63 | 25.67 | 26.65 | 27.53 | 28.12 | 28.42 | 28.44 | 28.64 | 30.35 | 32.80 | 31.86 | 31.45 | 30.84 | 29.82 |
| 9 | 27.23 | 28.64 | 29.95 | 31.11 | 31.76 | 32.24 | 32.46 | 32.84 | 34.86 | 37.81 | 36.90 | 36.49 | 35.79 | 34.58 |
| 10 | 29.64 | 31.46 | 32.96 | 34.43 | 35.44 | 36.09 | 36.42 | 36.87 | 39.14 | 42.45 | 41.48 | 41.02 | 40.31 | 39.07 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 41.478 |
| SC2 | 0 | 8 | 28.642 |
| SC3 | -18 | 7 | 23.793 |
| SC4 | -25 | 6 | 19.171 |
| SC5 | -34 | 6 | 18.471 |
| A | 2368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 2035 mm |
| E2 | 1018 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2368 mm |
|---|---|
| Width | 1350 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.