ED-450AE4-C21 C
63.59 kW
Defrost: None
Product code: ED-450AG4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 24,556 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 365.2 m² |
| Inner volume | 78.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 344 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 2,720 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 84.7 dB(A) |
| Energy class | C |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| ED-450AG4-C21 C | None |
|---|---|
| ED-450AG4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 25.34 | 27.00 | 28.53 | 29.74 | 30.66 | 31.18 | 31.36 | 32.23 | 34.39 | 37.48 | 36.76 | 36.50 | 36.13 | 35.59 |
| 5 | 30.67 | 33.22 | 35.55 | 37.61 | 39.08 | 39.79 | 40.30 | 41.28 | 44.00 | 47.96 | 46.97 | 46.54 | 45.89 | 44.77 |
| 6 | ≈ 35.24 | 38.62 | 41.39 | 44.22 | 46.33 | 47.78 | 48.59 | 49.72 | 52.97 | 57.78 | 56.60 | 56.08 | 55.24 | 53.74 |
| 7 | ≈ 31.15 | ≈ 42.17 | 47.05 | 50.73 | 53.57 | 55.58 | 56.77 | 58.12 | 61.93 | 67.52 | 66.22 | 65.57 | 64.53 | 62.65 |
| 8 | ≈ 18.99 | ≈ 47.35 | 52.27 | 56.86 | 60.50 | 63.16 | 64.82 | 66.47 | 70.85 | 77.25 | 75.87 | 75.12 | 73.91 | 71.65 |
| 9 | not rated | ≈ 48.00 | ≈ 57.06 | 62.60 | 67.10 | 70.45 | 72.69 | 74.72 | 79.69 | 86.93 | 85.52 | 84.70 | 83.33 | 80.75 |
| 10 | not rated | ≈ 29.23 | ≈ 61.44 | 67.96 | 73.37 | 77.50 | 80.37 | 82.83 | 88.44 | 96.56 | 95.15 | 94.27 | 92.78 | 89.91 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 95.146 |
| SC2 | 0 | 8 | 66.469 |
| SC3 | -18 | 7 | 51.968 |
| SC4 | -25 | 6 | 41.393 |
| SC5 | -34 | 6 | 35.976 |
| A | 4368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 4035 mm |
| E2 | 1018 mm |
| E3 | 1000 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 4368 mm |
|---|---|
| Width | 1350 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.