EG-A-223AC4-C21 C
1.25 kW
Defrost: None
Product code: EG-A-225AC6-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 916 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 3.7 m² |
| Inner volume | 0.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 9 kg |
| Quantity | 2 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 190 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 61.5 dB(A) |
| Energy class | E |
| Inlet | Ø3/8" |
|---|---|
| Outlet | Ø3/8" |
| EG-A-225AC6-C25 C | None |
|---|---|
| EG-A-225AC6-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.44 | 0.46 | 0.47 | 0.48 | 0.49 | 0.49 | 0.49 | 0.50 | 0.54 | 0.58 | 0.57 | 0.57 | 0.56 | 0.55 |
| 5 | 0.56 | 0.59 | 0.62 | 0.65 | 0.67 | 0.67 | 0.68 | 0.69 | 0.74 | 0.80 | 0.78 | 0.78 | 0.77 | 0.75 |
| 6 | 0.66 | 0.71 | 0.75 | 0.79 | 0.82 | 0.84 | 0.85 | 0.87 | 0.92 | 1.01 | 0.99 | 0.98 | 0.97 | 0.95 |
| 7 | 0.76 | 0.82 | 0.88 | 0.93 | 0.97 | 0.99 | 1.01 | 1.03 | 1.10 | 1.20 | 1.18 | 1.17 | 1.15 | 1.13 |
| 8 | ≈ 0.84 | 0.92 | 1.00 | 1.06 | 1.12 | 1.15 | 1.17 | 1.19 | 1.27 | 1.39 | 1.36 | 1.35 | 1.34 | 1.31 |
| 9 | ≈ 0.92 | 1.01 | 1.11 | 1.19 | 1.25 | 1.29 | 1.33 | 1.36 | 1.45 | 1.58 | 1.56 | 1.54 | 1.52 | 1.49 |
| 10 | ≈ 0.95 | ≈ 1.10 | 1.21 | 1.30 | 1.38 | 1.44 | 1.48 | 1.52 | 1.62 | 1.78 | 1.75 | 1.74 | 1.71 | 1.67 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 1.750 |
| SC2 | 0 | 8 | 1.194 |
| SC3 | -18 | 7 | 0.948 |
| SC4 | -25 | 6 | 0.751 |
| SC5 | -34 | 6 | 0.671 |
| A | 815 mm |
|---|---|
| B | 215 mm |
| C | 465 mm |
| F | 187 mm |
| E | 190 mm |
| D | 266 mm |
| D IN | 1 x Ø3/8" |
| D OUT | 1 x Ø3/8" |
| Length | 815 mm |
|---|---|
| Width | 465 mm |
| Height | 215 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.