EG-A-225AD4-C25 C
1.77 kW
Defrost: None
Product code: EG-A-323AC6-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,089 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 5.9 m² |
| Inner volume | 1.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 14 kg |
| Quantity | 3 |
|---|---|
| Diameter | 230 mm |
| Speed | 1,300 rpm |
| Power | 114 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 34.0 dB(A) |
|---|---|
| Sound power | 54.9 dB(A) |
| Energy class | D |
| Inlet | Ø3/8" |
|---|---|
| Outlet | Ø1/2" |
| EG-A-323AC6-C21 C | None |
|---|---|
| EG-A-323AC6-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.68 | 0.68 | 0.69 | 0.69 | 0.69 | 0.69 | 0.68 | 0.70 | 0.75 | 0.81 | 0.79 | 0.79 | 0.78 | 0.77 |
| 5 | 0.89 | 0.91 | 0.92 | 0.93 | 0.94 | 0.94 | 0.93 | 0.95 | 1.01 | 1.09 | 1.06 | 1.05 | 1.04 | 1.02 |
| 6 | 1.10 | 1.13 | 1.16 | 1.18 | 1.20 | 1.20 | 1.20 | 1.21 | 1.29 | 1.39 | 1.35 | 1.34 | 1.32 | 1.28 |
| 7 | 1.28 | 1.33 | 1.38 | 1.42 | 1.45 | 1.46 | 1.47 | 1.49 | 1.58 | 1.71 | 1.66 | 1.64 | 1.61 | 1.57 |
| 8 | 1.45 | 1.51 | 1.58 | 1.64 | 1.68 | 1.70 | 1.71 | 1.74 | 1.84 | 2.00 | 1.96 | 1.94 | 1.91 | 1.85 |
| 9 | 1.61 | 1.70 | 1.78 | 1.86 | 1.90 | 1.94 | 1.95 | 1.98 | 2.11 | 2.29 | 2.23 | 2.21 | 2.17 | 2.11 |
| 10 | 1.76 | 1.87 | 1.98 | 2.07 | 2.13 | 2.17 | 2.19 | 2.23 | 2.37 | 2.57 | 2.51 | 2.49 | 2.44 | 2.37 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 2.513 |
| SC2 | 0 | 8 | 1.735 |
| SC3 | -18 | 7 | 1.431 |
| SC4 | -25 | 6 | 1.155 |
| SC5 | -34 | 6 | 1.102 |
| A | 1205 mm |
|---|---|
| B | 215 mm |
| C | 465 mm |
| F | 187 mm |
| E | 365 mm |
| D | 441 mm |
| D IN | 1 x Ø3/8" |
| D OUT | 1 x Ø1/2" |
| Length | 1205 mm |
|---|---|
| Width | 465 mm |
| Height | 215 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.