Skip to Content

Unit cooler EG-130AE4-C21 C

Unit cooler EG-130AE4-C21 C
Illustrative photo

Producer: Karyer · Line: EG (General)

Product code: EG-130AE4-C21 C

Cooling capacity i
2.70 kW
Air flow
1,060 m³/h
Fin spacing
4.2 mm
Air throw
7 m
Fans
1 × ⌀300 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EG — EG - angled ceiling-type unit cooler
  • B
    Number of fans: 1 — Number of fans (one digit).
  • C
    Fan diameter: 30 — Ø300 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: E — 6 tube rows
  • F
    Fin spacing: 4 — Fin spacing about 4 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 21 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 1,060 m³/h
Air throw 7 m
External surface 11.8 m²
Inner volume 2.1 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 22 kg
Fans
Quantity 1
Diameter 300 mm
Speed 1,380 rpm
Power 62 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 45.0 dB(A)
Sound power 66.2 dB(A)
Energy class B
Connections
Inlet Ø9,52
Outlet Ø15,9
Defrost
EG-130AE4-C21 C None
EG-130AE4-C21 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
2.602 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 1.08 1.09 1.11 1.12 1.13 1.12 1.11 1.15 1.23 1.34 1.31 1.31 1.30 1.28
5 1.38 1.41 1.44 1.47 1.48 1.48 1.47 1.50 1.60 1.74 1.69 1.67 1.65 1.61
6 1.67 1.73 1.78 1.83 1.85 1.86 1.84 1.87 1.99 2.15 2.08 2.06 2.02 1.95
7 1.93 2.02 2.09 2.16 2.20 2.23 2.22 2.25 2.39 2.59 2.50 2.47 2.41 2.32
8 2.17 2.28 2.39 2.48 2.54 2.57 2.57 2.60 2.76 2.99 2.91 2.87 2.81 2.70
9 2.41 2.55 2.68 2.80 2.87 2.91 2.92 2.95 3.13 3.39 3.29 3.25 3.18 3.05
10 2.62 2.80 2.96 3.11 3.20 3.25 3.27 3.31 3.51 3.79 3.69 3.63 3.55 3.41

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 3.686
SC2 0 8 2.602
SC3 -18 7 2.181
SC4 -25 6 1.780
SC5 -34 6 1.685

Dimensions

Dimension drawing of EG-130AE4-C21 C
Dimension drawing
Dimensions as drawn
A 1146 mm
B 685 mm
C 245 mm
F 630 mm
E 835 mm
D IN 1 x Ø9,52
D OUT 1 x Ø15,9
Overall [mm]
Length 1146 mm
Width 685 mm
Height 245 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.