EG-225AE4-C23 C
3.13 kW
Defrost: None
Product code: EG-225BE4-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,125 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 17.7 m² |
| Inner volume | 3.0 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 27 kg |
| Quantity | 2 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 61.4 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø15,9 |
| EG-225BE4-C23 C | None |
|---|---|
| EG-225BE4-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.19 | 1.24 | 1.28 | 1.32 | 1.35 | 1.36 | 1.36 | 1.40 | 1.49 | 1.63 | 1.60 | 1.58 | 1.57 | 1.55 |
| 5 | 1.47 | 1.55 | 1.62 | 1.69 | 1.73 | 1.76 | 1.77 | 1.80 | 1.92 | 2.09 | 2.04 | 2.02 | 1.99 | 1.94 |
| 6 | 1.73 | 1.84 | 1.95 | 2.05 | 2.11 | 2.16 | 2.17 | 2.21 | 2.35 | 2.56 | 2.50 | 2.47 | 2.43 | 2.36 |
| 7 | 1.95 | 2.11 | 2.25 | 2.37 | 2.47 | 2.52 | 2.55 | 2.60 | 2.77 | 3.01 | 2.94 | 2.91 | 2.86 | 2.78 |
| 8 | ≈ 2.16 | 2.37 | 2.55 | 2.71 | 2.81 | 2.89 | 2.93 | 2.99 | 3.17 | 3.45 | 3.38 | 3.34 | 3.28 | 3.18 |
| 9 | ≈ 2.37 | 2.60 | 2.82 | 3.01 | 3.16 | 3.26 | 3.31 | 3.37 | 3.58 | 3.90 | 3.82 | 3.77 | 3.70 | 3.58 |
| 10 | 2.54 | 2.81 | 3.07 | 3.31 | 3.49 | 3.61 | 3.67 | 3.74 | 3.98 | 4.33 | 4.24 | 4.20 | 4.13 | 3.99 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.243 |
| SC2 | 0 | 8 | 2.985 |
| SC3 | -18 | 7 | 2.415 |
| SC4 | -25 | 6 | 1.950 |
| SC5 | -34 | 6 | 1.752 |
| A | 1066 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 378 mm |
| E | 755 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø15,9 |
| Length | 1066 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.