EG-325BB7-C23 C
2.83 kW
Defrost: None
Product code: EG-230AB7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,771 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 7.4 m² |
| Inner volume | 2.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 34 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 67.3 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø15,9 |
| EG-230AB7-C21 C | None |
|---|---|
| EG-230AB7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.03 | 1.02 | 1.01 | 1.01 | 1.01 | 1.00 | 0.98 | 1.00 | 1.05 | 1.13 | 1.10 | 1.09 | 1.08 | 1.05 |
| 5 | 1.38 | 1.39 | 1.40 | 1.41 | 1.41 | 1.41 | 1.39 | 1.40 | 1.49 | 1.61 | 1.56 | 1.55 | 1.52 | 1.49 |
| 6 | 1.72 | 1.76 | 1.79 | 1.83 | 1.85 | 1.85 | 1.84 | 1.85 | 1.96 | 2.12 | 2.06 | 2.04 | 2.00 | 1.96 |
| 7 | 2.01 | 2.08 | 2.15 | 2.21 | 2.25 | 2.28 | 2.29 | 2.32 | 2.46 | 2.67 | 2.60 | 2.57 | 2.53 | 2.46 |
| 8 | 2.30 | 2.40 | 2.48 | 2.56 | 2.62 | 2.66 | 2.68 | 2.71 | 2.89 | 3.14 | 3.07 | 3.04 | 3.00 | 2.94 |
| 9 | 2.56 | 2.69 | 2.81 | 2.92 | 3.00 | 3.04 | 3.08 | 3.12 | 3.31 | 3.60 | 3.53 | 3.50 | 3.45 | 3.37 |
| 10 | 2.80 | 2.97 | 3.12 | 3.26 | 3.37 | 3.43 | 3.48 | 3.52 | 3.75 | 4.07 | 3.99 | 3.96 | 3.90 | 3.81 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.991 |
| SC2 | 0 | 8 | 2.714 |
| SC3 | -18 | 7 | 2.226 |
| SC4 | -25 | 6 | 1.794 |
| SC5 | -34 | 6 | 1.727 |
| A | 1946 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø15,9 |
| Length | 1946 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.